Terminal
Cable requirements
Temperature inputs (connec-
tion cable)
☐ Number of insulated conductors for tolerance ±2°C: at least
two
☐ Number of insulated conductors for tolerance ±0.5°C: at least
four
☐ Conductor cross-section: at least 4 x 0.25 mm²
☐ External cable diameter: 4.5 mm to 7.0 mm
☐ Maximum cable length for four-conductor connection
technology: 20 m
☐ Maximum cable length for two-conductor connection
technology: 2.5 m
Inverter (Speedwire)
☐ Number of insulated conductor pairs and insulated conductor
cross-section: at least 2 x 2 x 0.22 mm²
☐ External diameter: the maximum external diameter depends on
the size of the cable gland or the conduit (see the installation
manual of the Speedwire/Webconnect interface)
☐ Cable type: 100BaseTx, from Cat5 with shielding S-UTP, F-UTP
or higher
☐ Plug type: RJ45 of Cat5, Cat5e, Cat6, Cat6a
Cat7 plugs cannot be used.
☐ Cable length between two nodes: max. 50 m with patch cable,
max. 100 m with installation cable
LAN
☐ Number of insulated conductor pairs and insulated conductor
cross-section: at least 2 x 2 x 0.22 mm²
☐ Cable type: 100BaseTx, from Cat5 with shielding S-UTP, F-UTP
or higher
☐ Plug type: RJ45 of Cat5, Cat5e, Cat6 or Cat6a. Cat7 plugs
cannot be used.
☐ Cable length between two nodes: max. 50 m with patch cable,
max. 100 m with installation cable
6.4
Performing Pin Coding
Pin coding prevents confusion when using multipole connectors, e.g. in the event of removal and
later re-insertion of a multipole plug. Using the coded pins, you can be sure of inserting a multipole
plug into the correct terminal. Tip: perform pin coding for all multipole connections now, even if you
do not wish to use all multipole connections at this point. Then you will not need to perform pin
coding later for the multipole connections that you are not currently using.
Code the pins correctly
When selecting the pins to be coded, be sure to code different pins for each terminal and for
each pin row.