Electrical Connection
SMA
Solar Technology AG
Page 24
BATFUSE-TEN082310
Technical Description
9.
Connect the Sunny Island to the top side of the BatFuse and the battery and charge controller
to the bottom side.
Screw the pipe cable lugs to the appropriate connection terminals and tighten each screw at
20 Nm.
5.3 Using or Replacing NH Fuses
DANGER!
Risk of lethal electric arcs
•
Only after completing
all
installation and maintenance work in the system
you should insert the NH fuses or close the load disconnection unit.
•
NH fuses must not be inserted or pulled under load.
•
Separate all consumers from the grid.
•
All Sunny Island AC input power sources should be disconnected before working
on the BatFuse.
•
Observe all relevant safety guidelines set forth by the professional association.
Information
Observe the instructions in the sections Initial Start-Up and Electrical Connection of the
technical instructions of the Sunny Island.
Underneath
Top