36
SMC9-11TLRP-IA-en-51
Installation Manual
6 Electrical Connection
SMA Solar Technology AG
9. Connect the AC cable to the terminal block for the AC cable using a screwdriver:
• Connect PE to terminal
PE
.
• Connect N to terminal
N
.
• Connect L to terminal
L
.
10. Close the inverter and earth the enclosure lid:
☑ The teeth of the conical spring washers are pushed into the enclosure lid. This ensures that
the enclosure lid is earthed.
• Attach one conical spring washer to each
screw. The grooved side of the conical spring
washer must point to the screw head.
• Secure the enclosure lid with screws in the
sequence 1 to 6 (torque: 6 Nm).