Name
Description
Range
Explanation
Default value
HzCtllLim
Threshold for underfre-
quency level 1
45 Hz to 50 Hz
For 50 Hz grid
49 Hz
55 Hz to 60 Hz
For 60 Hz grid
58.8 Hz
HzCtllLimTm
Delay time for underfre-
quency level 1
0 ms -
to 1,000,000 ms
‒
1,000 ms
HzCtlllLim
Threshold for underfre-
quency level 2
45 Hz to 50 Hz
For 50 Hz grid
48 Hz
55 Hz to 60 Hz
For 60 Hz grid
58 Hz
HzCtlllLimTm
Delay time for underfre-
quency level 2
0 ms -
to 1,000,000 ms
‒
600 ms
HzCtlMin
Threshold for underfre-
quency level 3
45 Hz to 50 Hz
For 50 Hz grid
47 Hz
55 Hz to 60 Hz
For 60 Hz grid
57 Hz
HzCtlMinTm
Delay time for underfre-
quency level 3
0 ms -
to 1,000,000 ms
‒
600 ms
NormVac*
Measuring range end
value of AC voltage
measurement
1 V to 1,000 V
‒
862 V
NormAac*
Measuring range end
value of AC current mea-
surement
1 A to 3,000 A
‒
2,219 A
ManResOvrVol Manual activation after
overvoltage
Off
Deactivated
Off
On
Activated
ManResUn-
drVol
Manual activation after
undervoltage
Off
Deactivated
Off
On
Activated
ManResOvrFrq Manual activation after
overfrequency
Off
Deactivated
Off
On
Activated
ManResUn-
drFrq
Manual activation after
underfrequency
Off
Deactivated
Off
On
Activated
ManResPID
Manual activation after
interruption by passive is-
landing detection
Off
Deactivated
Off
On
Activated
ManResPLD
Manual activation after
interruption due to distur-
bance in a line conduc-
tor
Off
Deactivated
Off
On
Activated
* You can only view this parameter after entering the installer password.
14 Operating Data and Parameters
SMA Solar Technology AG
System Manual
231
MVPS22JP-SH-en-11