14 Operating Data and Parameters
The information in the following sections affect the inverters only. Information on the operating data and parameters of
further optional devices of the MV Power Station, such as the medium-voltage switchgear or the control device for
cascade control, can be found in the documentation of the respective device.
14.1
Operating Data
14.1.1 Inverter
14.1.1.1 Power Limitation
Errors and warnings relating to active power limitation
Name
Display
Description
P-WModFailStt
Off
No mode for active power limitation has been selected.
Ok
A mode for active power limitation has been selected and no error is
present.
ComFail
The mode
WCtlCom
has been selected and the expected signal with
a valid active power limitation has been absent for at least five min-
utes.
AnInFail
The mode
WCnstNomAnIn
has been selected and the value mea-
sured at the analog input is less than 2 mA.
ComInvalid
The mode
WCtlCom
has been selected and there is invalid content
in the power setpoint information.
14 Operating Data and Parameters
SMA Solar Technology AG
System Manual
MVPS22JP-SH-en-11
214