background image

22

Sentry

3. Water lines:  slightest leaks should be corrected.
4. Low water cutoff, for operation (see instructions fur-

nished with unit).

2.  WATER LEVEL CHECK DURING HEATING SEASON

A. Check water pressure regularly and add water slowly to

system when needed. If much water is added, venting
may be necessary.

B. Regular loss of water from water boiler system may indi-

cate either a system leak, or a faulty air control system,
or a faulty automatic fill valve.

3. ANNUAL INSPECTION AND CLEANING

A. It is important that this boiler be inspected by a compe-

tent serviceperson to help insure safe and reliable oper-
ation.

B. Check for gas leaks from valve and gas piping to burners

and pilot. If leaks are found, repair or replace as required.

C. This inspection should include:

1. Controls check.  See “Safety Check for Control 

System” (No. 4) below.

2. Recheck of input gas rate to burners.  See "Initial

Start" paragraph in "Operating instructions" section.

3. Re-adjusting for best flame characteristics of main

flame and pilot(s).
See "Initial Start" paragraph in "Operating
Instructions" section and see "Burner Adjustment"
section.

4. Burner and boiler flue passage cleanliness:

BURNER AND FLUE CLEANING (see figure 17).  It is
suggested that paper be placed on burners to collect
any foreign material when cleaning flues.

5. Remove jacket top and flue cover.  
6. Use wire brush to clean flueways.
7. Replace flue cover and re-seal with furnace cement.

Replace jacket top.  Remove and dispose of paper
and accumulated material.

8. If burner surfaces are not clean, or if uneven flame

indicates plugged burner ports, remove and clean
burners.

NOTE-TO REMOVE BURNERS:

1. Disconnect pilot at pilot mount, or disconnect pilot gas

line at gas valve, before removing burners next to pilot.

2. Lift burner and remove burner from orifice.
3. Clean and replace burners* and pilot.  Adjust burners as

described on page 10.

* To clean burners run a clean flue brush up the tube until all foreign

matter is removed.

4. SAFETY CHECK FOR CONTROL SYSTEM

A. High limit control test:  Set thermostat high enough for

boiler water temperature to reach high limit control set-
ting.  When this temperature is reached, the high limit
switch should open, and the main gas valve should close

automatically.  If the high limit does not operate to close
the main gas valve, the valve, the high limit or the wiring
is faulty.  Repair or replace immediately.

B. Gas valve safety shutdown test:

For boilers equipped with Honeywell S8600 intermittent 
pilot system, with main burners firing, disconnect the
ignition cable from the S8600 IGNITOR BOX.  The gas 
valve should shut off the main burners.
If the gas valve fails to shut down main burners when the
test is performed, replace the gas valve.

C. Check for gas leaks from valve and gas piping to burners

and pilot. If leaks are found, repair or replace as required.

5. PROVIDING PROTECTION FROM FREEZING

A. Anti-freeze is sometimes used in hydronic heating sys-

tems to protect against freeze-up in the event of power
failure or control shutdown when the building is unoccu-
pied.  It should be recognized that unless the building is
kept above freezing temperature by some means, the
plumbing system is not protected.
PROPYLENE GLYCOL is used in the quick-freeze food 
industry; it is practically non-toxic. Its use may be permit-
ted when tankless heaters are used. When anti-freeze 
must be used, inhibited propylene glycol is recommend-
ed.  Useful information on the characteristics, mixing
proportions, etc. of  glycol in heating systems is given in
Technical Topics No. 2A, available from the Hydronics 
Institute 34 Russo Place, Berkeley Heights, NJ 07922. 
Consult glycol manufacturers for sources of propylene 
glycol. DO NOT use ethylene glycol because it is toxic.

B. Water Treatment:

A good water treatment program will not only extend the
useful life of this boiler but it will also save much of the
time and expense of repairs made necessary by pre-
ventable occurrences.
A reputable water treatment company should be consult-
ed to evaluate and determine the best overall treatment
program for your boiler equipment.

6. KEEP THE BOILER AREA CLEAR AND FREE FROM

COMBUSTIBLE MATERIALS, GASOLINE, AND OTHER
FLAMMABLE VAPORS AND LIQUIDS.

WARNING:

The ceramic combustion chamber in the burner box
contains crystalline silica. 

Wear proper dust mask and gloves when servicing 
combustion chamber or burners. 

Crystalline Silica has been identified as a carcinogen or
possibly carcinogenic to humans.

Summary of Contents for S-34

Page 1: ...atest edition The installation must also conform to the additional requirements in this Slant Fin Instruction Book In addition where required by the authority having jurisdic tion the installation mus...

Page 2: ...entry Note Height dimension increases by 1 3 4 when comustible floor kit is used Vent damper may be installed horizontally on all models with use of a vent elbow For more information see figure 2 page...

Page 3: ...it containing electric wires or telephone cables consult local codes or the National Board of Fire Underwriters for specific requirements S 34 2 81 8 145 8 4 33 61 4 190 S 60 3 111 8 175 8 4 37 41 2 2...

Page 4: ...1 NFPA 54 latest edition which will be referred to as the National Fuel Gas Code Local codes apply If a masonry chimney is exposed to the outdoors on one or more sides below the roof line exterior chi...

Page 5: ...e connector to the out door chimney or vent as close to the draft hood as practi cable and without modification of the draft hood or the vent damper See figures 1 2 and 3 2 The inlet size of the vent...

Page 6: ...supply otherwise shock or death can result 1 Power Supply A separately fused circuit is recommended Use a standard 15 amp fuse or breaker and 14 gage conductors in BX cable or conduit Provide disconn...

Page 7: ...ITS EQUIVALENT IGNITER CABLE PILOT GAS PIPE ELECTRIC IGNITION PILOT CIRCULATOR BLOCKED VENT SAFETY SWITCH ROLL OUT SWITCH L2 L1 C1 C2 B1 IGNITION MODULE 24V GND 24V I2 B2 VENT DAMPER HARNESS I1 WIRE...

Page 8: ...8 Sentry Figure 5 Multizoning of Sentry boilers pump zoning system using R845A relay Figure 6 Multizoning of Sentry boiler 2 zone system pump zoning system using R882A B relays...

Page 9: ...9 Sentry Figure 7 Multizoning of Sentry boilers zone valve system using V8043E F zone valves Figure 8 Multizoning zone valve system with indirect water heater DHW Priority using R882A B relay...

Page 10: ...10 Sentry Figure 9 Single zone with indirect water heater DHW Priority using R882A B relay...

Page 11: ...orks below If the heating system is unable to supply needed heat to the house the ECONOMY Dial should be turned to a lower setting example In a three zone house turn the dial to 2 or 1 Conversely if t...

Page 12: ...in the display as Pro 2 Turn the HI TEMP dial to select feature 2 3 Push the Test Settings Button to c for Celsius or F for Fahrenheit 4 Reset LO TEMP and HI TEMP settings to desired temperatures see...

Page 13: ...al to access the Program Mode indicated in the display as Pro 2 Turn the HI TEMP dial to select feature 5 3 Push the Test Settings Button to turn Circulator Hold Off or OFF 4 Reset LO TEMP and HI TEMP...

Page 14: ...ve OFF 2 Fahrenheit or Celsius F c Degrees Fahrenheit Degrees Celsius F 3 LWCO Manual or Automatic Reset A b Automatic Reset Manual Reset A 4 Circulator Options A b C Circulator operation on T TV call...

Page 15: ...oiler operation TEST SETTINGS Button ToTest Low Water Cut Off Press and hold the Test Settings but ton for 5 seconds The display will read LCO LWCO TEST LCO The red Low Water light should illuminate a...

Page 16: ...BURNERS OFF VENT DAMPER CLOSES CIRCULATOR OFF SYSTEM GOES TO STANDBY SPARK GENERATOR MODULE POWERED S8600F OR S8600M IGNITION SPARK STARTS AND PILOT VALVE OPERATOR OPENS S8670E IGNITION SPARK AND PIL...

Page 17: ...larger capacity tank Locate the tank near the boiler as illustrat ed An automatic air vent should be installed in the top of the boiler or air purger See figure 10 B PUMP LOCATION Locating low head p...

Page 18: ...18 Sentry Figure 11 Zoning with circulators optional indirect DHW tank...

Page 19: ...19 Sentry Figure 12 Zoning with zone valves optional indirect DHW tank...

Page 20: ...mell for gas including near the floor If you then smell gas STOP Follow B in the safety information above on this page If you don t smell gas go to next step 8 Turn gas control knob counterclockwise t...

Page 21: ...ce at maximum oper ating temperature after prolonged operation NOTE Observe operation of the pilot burner with appli ance doors in the final operating position Use of a mir ror may be helpful 2 Safety...

Page 22: ...perature is reached the high limit switch should open and the main gas valve should close automatically If the high limit does not operate to close the main gas valve the valve the high limit or the w...

Page 23: ...orizontal run of smokepipe 4 Inadequate chimney or venting system REMEDY 1 Check clean re light See instructions 2 Open gas valve s 3 Close switch 4 Replace fuse 5 Check control Clean contacts or repl...

Page 24: ...er level in boiler Remove and check sensor to ensure metal to metal contact between sensor and inside surface of well Has the event damper opened Control will not fire burner if damper did not fully o...

Page 25: ...y hot water to heating coils in air handling units flow control valves or other devices must be installed to prevent gravity circulation of water in the coils dur ing the cooling cycle IF REPLACEMENT...

Page 26: ...ing after 5 min utes of main burner operation Use the flame of a match or candle or smoke from a cigarette cigar or pipe f After it has been determined that each appliance remaining connected to the c...

Page 27: ...27 Sentry...

Page 28: ...CORPORATION Greenvale N Y 11548 Phone 516 484 2600 FAX 516 484 0933 Canada Slant Fin LTD LTEE Mississauga Ontario www slantfin com Slant Fin Corp 2017 Printed in the U S A 317 Publication No S 42 P N...

Reviews: