11

Sentry

Diagnostic LEDs

Low Temperature

Limit Setting 

(OFF or 110°-220°F)

Factory OFF

High Temperature

Limit Setting 

(100°-220°F)

Factory 190°F

Spade Connectors
for OS-100 Outdoor
Sensor Kit

Economy Dial
(OFF or LO, 1, 2, 3,
4, 5, HI)
Factory 1

Differentials are au-
tomatic and will vary
based on control set-
tings and boiler tem-
perature.

Indicator Light
(announces heat call)

Jumper

Test/Settings
Button

Dynamic 

Display

Water Temperature

and Real Time 

Verification of Setting

Adjustments.

Vent Damper 

Receptacle

NOTE:

Settings can be checked

using the TEST/SETTINGS Button.

SETTING THE HIGH LIMIT

The high limit is factory set at
190°F. To adjust, turn the HI
TEMP Dial

A

until the desired

setting is displayed. (Setting
range: 100°-220°F)

SETTING THE LOW LIMIT

The low limit is designed to main-
tain temperature in boilers
equipped with tankless coils used
for domestic hot water. The low
limit is factory set to OFF. Prior to
adjusting, remove the jumper (not
equipped on all units)  

. Then

turn the LO TEMP Dial   

C

clock-

wise until the desired temperature is displayed. For
proper operation, the low temperature limit setting
should be at least 10° below the high limit setting.
NOTE: For cold start operation, the low limit must be
turned OFF. IMPORTANT: If low limit temperature can-
not be set above 140°F, remove jumper  

B

. (Setting

range: OFF or 110°-200°F).

SETTING THE ECONOMY FEATURE

The Economy Feature is factory set for a 1 zone heating system.
To adjust, turn the ECONOMY Dial  

D  

until the number dis-

played equals the number of heating zones. Do not include indi-
rect water heaters in the number of heating zones. The Economy
Feature conserves fuel by reducing boiler temperature (see “How
Thermal Targeting Works” below). If the heating system is unable
to supply needed heat to the house, the ECONOMY Dial should
be turned to a lower setting (example: In a three zone house, turn
the dial to 2 or 1). Conversely, if the boiler provides adequate
heat, added fuel savings can be achieved by selecting a higher
setting (example: 4 or 5). If the heating and indirect water heater
signals were not separated when wiring the control, the Economy
Feature should be turned OFF to insure the boiler supplies ade-
quate temperature to heat the indirect tank.

SETTING THE CONTROL

BOILERS EQUIPPED WITH HYDROSTAT CONTROL

SETTING

OFF

Disables economy function. Will allow boiler to fire until hi 
limit temp is reached and re-fire with a 10° subtractive
differential.

LO

Provides lowest level of fuel savings. Use this setting only
if the house does not stay warm at higher settings.

1

Recommended setting for single zone systems

2

Recommended setting for Two zone systems

3

Recommended setting for Three zone systems

4

Recommended setting for Four zone systems

5

Recommended setting for Five zone systems

HI

Provides highest level of fuel savings

IMPORTANT NOTICE

This boiler is equipped with a feature that saves energy by reducing the boiler water
temperature as the heating load decreases. This feature is equipped with an over-
ride which is provided primarily to permit the use of an external energy manage-
ment system that serves the same function. THIS OVERRIDE MUST NOT BE
USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE:
• An external energy management system is installed that reduces the boiler water
temperature as the heating load decreases.
•This boiler is not used for any space heating.
•This boiler has an input of 300,000 BTU/hr or greater
• This boiler is part of a modular or multiple boiler system having a total input of
300,000 BTU/hr or greater.
• This boiler is equipped with a tankless coil.

Summary of Contents for S-34

Page 1: ...atest edition The installation must also conform to the additional requirements in this Slant Fin Instruction Book In addition where required by the authority having jurisdic tion the installation mus...

Page 2: ...entry Note Height dimension increases by 1 3 4 when comustible floor kit is used Vent damper may be installed horizontally on all models with use of a vent elbow For more information see figure 2 page...

Page 3: ...it containing electric wires or telephone cables consult local codes or the National Board of Fire Underwriters for specific requirements S 34 2 81 8 145 8 4 33 61 4 190 S 60 3 111 8 175 8 4 37 41 2 2...

Page 4: ...1 NFPA 54 latest edition which will be referred to as the National Fuel Gas Code Local codes apply If a masonry chimney is exposed to the outdoors on one or more sides below the roof line exterior chi...

Page 5: ...e connector to the out door chimney or vent as close to the draft hood as practi cable and without modification of the draft hood or the vent damper See figures 1 2 and 3 2 The inlet size of the vent...

Page 6: ...supply otherwise shock or death can result 1 Power Supply A separately fused circuit is recommended Use a standard 15 amp fuse or breaker and 14 gage conductors in BX cable or conduit Provide disconn...

Page 7: ...ITS EQUIVALENT IGNITER CABLE PILOT GAS PIPE ELECTRIC IGNITION PILOT CIRCULATOR BLOCKED VENT SAFETY SWITCH ROLL OUT SWITCH L2 L1 C1 C2 B1 IGNITION MODULE 24V GND 24V I2 B2 VENT DAMPER HARNESS I1 WIRE...

Page 8: ...8 Sentry Figure 5 Multizoning of Sentry boilers pump zoning system using R845A relay Figure 6 Multizoning of Sentry boiler 2 zone system pump zoning system using R882A B relays...

Page 9: ...9 Sentry Figure 7 Multizoning of Sentry boilers zone valve system using V8043E F zone valves Figure 8 Multizoning zone valve system with indirect water heater DHW Priority using R882A B relay...

Page 10: ...10 Sentry Figure 9 Single zone with indirect water heater DHW Priority using R882A B relay...

Page 11: ...orks below If the heating system is unable to supply needed heat to the house the ECONOMY Dial should be turned to a lower setting example In a three zone house turn the dial to 2 or 1 Conversely if t...

Page 12: ...in the display as Pro 2 Turn the HI TEMP dial to select feature 2 3 Push the Test Settings Button to c for Celsius or F for Fahrenheit 4 Reset LO TEMP and HI TEMP settings to desired temperatures see...

Page 13: ...al to access the Program Mode indicated in the display as Pro 2 Turn the HI TEMP dial to select feature 5 3 Push the Test Settings Button to turn Circulator Hold Off or OFF 4 Reset LO TEMP and HI TEMP...

Page 14: ...ve OFF 2 Fahrenheit or Celsius F c Degrees Fahrenheit Degrees Celsius F 3 LWCO Manual or Automatic Reset A b Automatic Reset Manual Reset A 4 Circulator Options A b C Circulator operation on T TV call...

Page 15: ...oiler operation TEST SETTINGS Button ToTest Low Water Cut Off Press and hold the Test Settings but ton for 5 seconds The display will read LCO LWCO TEST LCO The red Low Water light should illuminate a...

Page 16: ...BURNERS OFF VENT DAMPER CLOSES CIRCULATOR OFF SYSTEM GOES TO STANDBY SPARK GENERATOR MODULE POWERED S8600F OR S8600M IGNITION SPARK STARTS AND PILOT VALVE OPERATOR OPENS S8670E IGNITION SPARK AND PIL...

Page 17: ...larger capacity tank Locate the tank near the boiler as illustrat ed An automatic air vent should be installed in the top of the boiler or air purger See figure 10 B PUMP LOCATION Locating low head p...

Page 18: ...18 Sentry Figure 11 Zoning with circulators optional indirect DHW tank...

Page 19: ...19 Sentry Figure 12 Zoning with zone valves optional indirect DHW tank...

Page 20: ...mell for gas including near the floor If you then smell gas STOP Follow B in the safety information above on this page If you don t smell gas go to next step 8 Turn gas control knob counterclockwise t...

Page 21: ...ce at maximum oper ating temperature after prolonged operation NOTE Observe operation of the pilot burner with appli ance doors in the final operating position Use of a mir ror may be helpful 2 Safety...

Page 22: ...perature is reached the high limit switch should open and the main gas valve should close automatically If the high limit does not operate to close the main gas valve the valve the high limit or the w...

Page 23: ...orizontal run of smokepipe 4 Inadequate chimney or venting system REMEDY 1 Check clean re light See instructions 2 Open gas valve s 3 Close switch 4 Replace fuse 5 Check control Clean contacts or repl...

Page 24: ...er level in boiler Remove and check sensor to ensure metal to metal contact between sensor and inside surface of well Has the event damper opened Control will not fire burner if damper did not fully o...

Page 25: ...y hot water to heating coils in air handling units flow control valves or other devices must be installed to prevent gravity circulation of water in the coils dur ing the cooling cycle IF REPLACEMENT...

Page 26: ...ing after 5 min utes of main burner operation Use the flame of a match or candle or smoke from a cigarette cigar or pipe f After it has been determined that each appliance remaining connected to the c...

Page 27: ...27 Sentry...

Page 28: ...CORPORATION Greenvale N Y 11548 Phone 516 484 2600 FAX 516 484 0933 Canada Slant Fin LTD LTEE Mississauga Ontario www slantfin com Slant Fin Corp 2017 Printed in the U S A 317 Publication No S 42 P N...