                             P/N 473915000

      

BOILER START-UP

WARNING

•  Do not set combustion visually.
•  Do not start burner unless all clean-out doors are 

secured in place.

•  Do not attempt to start burner when excess oil 

has accumulated, when unit is full of vapor, or 

when combustion chamber is very hot.

!

  

Boiler Start-Up Information

•  Have a qualified service technician perform the startup 

procedures. Refer to boiler Installation, Operation & 

Maintenance Manual for full details.

•  Instruments are the only reliable method to determine 

proper combustion adjustments. An improperly 

adjusted burner causes soot and high fuel bills due to 

incomplete combustion of fuel oil. This may require 

excessive boiler maintenance, service costs, and in 

some instances, house cleaning or redecorating.

•  ¼” NPT plug is provided in burner swing door to take 

draft readings in combustion chamber. 

•  Chimney vent only, does not apply to direct vent 

boilers. ¼” diameter hole is required in the flue pipe 

between boiler and barometric damper to take draft, 

CO

2

, smoke and temperature readings. 

•  Adjust air shutter on oil burner to obtain “trace” 

of smoke. Measure CO

2

 at this point. Increase air 

adjustment to lower CO

2

 by  one-half (1/2) percent to 

one (1) percent. 

•  Verify zero (0) smoke and correct draft is obtained for 

installed unit. Reference boiler Installation, Operation 

& Maintenance Manual for correct draft settings. If 

proper draft can not be maintained, changes and/or 

modifications may be required in venting or chimney.

Restarting after Ignition Failure (Lockout

)

Riello Oil Burners:

•  Lockout is indicated by red reset button illuminating on 

oil burner primary control. Press and release red reset 

button ONCE to reset the control. If there is call for 

heat burner will start.

•  Burner goes into lockout second time, or fails to 

operate after reset button is pushed, contact qualified 

service technician to service boiler.

Summary of Contents for 473915000

Page 1: ...ithin the required clearance to combustibles 4 Ensure the supply of combustion air to the appliance is not obstructed or cut off Ensure the proper ventilation to the appliance area is maintained 5 Do not tamper with unit or controls call your service agent WARNING Maintenance and Service must be completed by qualified agency Modification substitution or elimination of factory equipped supplied or ...

Page 2: ...ustion chamber Chimney vent only does not apply to direct vent boilers diameter hole is required in the flue pipe between boiler and barometric damper to take draft CO2 smoke and temperature readings Adjust air shutter on oil burner to obtain trace of smoke Measure CO2 at this point Increase air adjustment to lower CO2 by one half 1 2 percent to one 1 percent Verify zero 0 smoke and correct draft ...

Page 3: ...ee of dirt lint and oil to maintain proper air fuel requires to burn Boiler Cleaning Instructions Have a qualified service technician perform cleaning Shut off all electrical power to boiler burner and shut off fuel supply Remove 4 bolts for access to combustion chamber If boiler is equipped with flexible fuel lines swing door open Remove vent connector Remove baffles for cleaning 4 5 6 section bo...

Page 4: ... qualified service technician before remodeling for annual service maintenance before extended periods of shutdown and before start up SLANT FIN CORPORATION Greenvale N Y 11548 Phone 516 484 2600 FAX 516 484 0933 Canada Slant Fin LTD LTEE Mississauga Ontario ...

Reviews: