SKYLUX Skycom CE MASTER User Manual And Installation Instructions Download Page 9

01/10/2016

9/26

E_MH_Installation_instruction_Skycom_Skymax_CE

b. Jumper J2 in pos. “Ext 3 wire” (Setting for Skymax

®

 standard / Cintramax

®

 CE (old) / Skyvent

®

 CE)

 
Unknown motor: line monitoring (1-3) with 3 wired motor connexion.
With jumper J3 (actuator output): you choose how many lines (number of 27KΩ)
you wish to detect - the same way as the motor line. 
This setting demands 3 wire cable from motor output to motor. 

c. Jumper J2/J3 is not mounted - No line monitoring for actuator output

Electronic current limiter, type LIP function and setting (Skylux 160°CE, Cintramax CE, Skymax CE)

The current limiter type LIP (mounted on the opening system) is used as current limiter for the actuator. On the LIP5, and 
younger version max. 3 times overload cut outs in the same direction is allowed. After which it will not be possible to run 
in this direction again, before the motor has run in the opposite direction. Please note that when opening, the red LED in 
the LIP must light. This indicates that polarity of the actuator is correct.

Table of LIP settings

* SA Power LM Large - parallel operation: Jumper OPT mounted - both motors stop at the same time if one stops  
   because of overload.
** When DIP4 is OFF = Tandem Mode - both motors stop at the same time if no current flows in one (1,5 sec. reaction        
   time).
*** Required: an actuator with “read” sensor (3-wire sensor black cable included). 

Actuator

24V Out

1

+

2

1

Line 1

-

3

2

3

4

J2

J3

Mn

M2

M1

Actuator 

Motor line monitor 
Ext 3 wire monitor

(line 1) 

27K Ohm

(Only last

actuator)

Opening system

Skylux 160° LM

Skylux 160° LM

Skylux 160°: Mini + RM

Cintramax

Skymax

current limit

3A

4A

2,5A

DIP 1

ON

OFF

ON

DIP 2

OFF

ON

ON

Type

DIP 1  DIP 2 DIP 3

DIP 4

DIP 5

DIP 6

DIP 7

DIP 8

LIP5
Single

See diagram

above

27K

ON

not present 

LIP6 *
Double

ON

OFF ** =

Tandem

27K ON

M1-M2  delay=OFF

not present

LIP7
Single
Basic

27K

ON

not present 

LIP7
Single

Tandem

27K

ON

ON =
COM

OFF = Slave

ON = Master

OFF = Synchro Mode

ON = Tandem Mode

off: no delay
on: 7s delay 

no function

1

2

1

3

2

3

4

J2

J3

M1

Actuator 

Motor line monitor 
Ext 3 wire monitor

(line 1) 

ENGLISH

Summary of Contents for Skycom CE MASTER

Page 1: ...Release 10 2016 SMOKE AND HEAT EXTRACTION CONTROL EN Skycom Skymax CE 24V 5A User manual and installation instructions ENGLISH...

Page 2: ...gs p 5 General description p 6 Installation p 6 Connection operation and settings p 8 Motor actuator p 8 Fire switches p 10 External priority switch p 11 Smoke heat detectors p 12 Comfort ventilation...

Page 3: ...n SHE systems are legally required in specific buildings In such buildings only CE certified systems in accordance with European and Belgian norms are allowed to be used At the same time our SHE syste...

Page 4: ...s automatically SKYCOM MASTER Art nr 30975 with Skymax CE without positive safety does NOT open automatically Cable sections in function of the distance SKYCOM MASTER Art nr 30975 SKYCOM SLAVE Art nr...

Page 5: ...e routes make sure the firemen can reach easily the fire place See to the possibility of a quick signal to the fire department in case of fire by a full fire detection system Consult your architect co...

Page 6: ...ailable on outputs for con nection with other systems AFA systems Air gates buzzer in the building We advise to consult your fire department to choose the best installation place fort all SHE accessor...

Page 7: ...DETECTOR COMFORT VENTILATION SMOKE AND HEAT SENSOR 1 2 3 4 6 5 7 4 x 0 5 mm 2 fireproof 6 x 0 5 mm 2 2 x 0 5 mm 2 3 x 0 5 mm 2 3 x 0 5 mm 2 standard standard fireproof fireproof Max 5m fireproof 2 x...

Page 8: ...ramax CE Known motor line monitoring 2 3 with double wired motor connexion Jumper J3 actuator output is set according to the number of termination resistors 27K to be detected 1 to max 4 lines can be...

Page 9: ...ng the red LED in the LIP must light This indicates that polarity of the actuator is correct Table of LIP settings SA Power LM Large parallel operation Jumper OPT mounted both motors stop at the same...

Page 10: ...ast switch in order to establish the line monitoring correctly this can either be done by moving the factory mounted resistor from the terminal strip to the last fire switch or connect jumper J1 in th...

Page 11: ...3 and open 1 4 outputs of the add on PCB and is indicated by LD3 and LD2 Therefore in the priority switch 10k resistors are integrated To avoid confusion there can be only one priority switch Informat...

Page 12: ...pening time after that nothing happens Continuous up signal gives 3x10 sec 30 sec One press on down closes the actuator completely it takes 18s longer compared to fully closing time In order to avoid...

Page 13: ...open 10 k Supplied with Panel Weather sensor Close all function Install the rain and wind detection as close as possible to the smoke hatch at a place where the wind speed is equal to the wind speed...

Page 14: ...cription for control units connected with bus connection If more control units are connected by means of a bus connection the following are monitored communicated between the control units A detected...

Page 15: ...close DIP 7 On the motor output opens shortly 3 seconds once a week and closes immediately after This function is used to give the right tension on the smoke vents to keep them airtight Function of h...

Page 16: ...ire monitor line 1 Next LIP Brown Blue only la Red 2 5mm2 Batteries 2x 12V 7 2 Ah Black 2 5mm2 Potential free NO NC contacts Max 48V 0 5A PS1 Power Supply 180 250 VAC 24VDC 150W 200W Potmeter comfort...

Page 17: ...Potmeter for comfort features OFF ON unted J9 7 J1 6 7 6 J1 7 6 ntrol or line ol point VT No 1 T 2 3 27k 13 14 10k 16 17 10k 1 3 10k 1 4 10k POWER OPEN CLOSE SVM addon 5 4 3 2 1 6 PRIOR CLOSE OPEN 1...

Page 18: ...1 5mm 24VDC 1 2 3 4 limit switch LIP 2x1 52mm Fireproof Max 5m 5 6 M Blue Brown 7 8 M Blue Brown POWER OPEN CLOSE SVM addon 5 4 3 2 1 6 Priority switch Remove resistors when mounting priority switch C...

Page 19: ...P 10 Bus comfort ON The control reacts on comfort signal via bus activity The control does not react on comfort signals via bus activity Always reaction on weather signal and failures via bus activity...

Page 20: ...E_MH_Installation_instruction_Skycom_Skymax_CE 01 10 2016 20 26 FRONT PANEL LED s MASTER SLAVE BUTTONS MASTER ONLY RESET SKYMAX...

Page 21: ...d connector keypad fail J9 Check settings arrows and connections according the schemes Yes Only close Blue lights when smoke vents are open flashes when the smoke hatch opens or closes Yes Yes lights...

Page 22: ...or 2 x 0 5 mm Cable between control units bus 3 x 0 5 mm Priority switch 4 x 0 5 mm Supply for control 230VAC 3 x 1 5 mm Comfort ventilation button 3 x 0 5 mm Wind and rain sensor 3 x 0 5 mm Only to b...

Page 23: ...is activated should not be carried out if the wind is more than 6 m sec as there might be a risk that the opening system cannot close automatically Control of the batteries If the batteries are replac...

Page 24: ...ll versions until 2014 35370 Main board Skycom CE all versions from 2015 31786 Main Board Skycom CE Slave until 2014 until stock lasts 31783 Power supply 230 VAC 28 5 VDC 8A 31784 Circuit breaker 10A...

Page 25: ...numbers of items to which this declaration relates is in conformity with the following standard s or other normative document s EN12101 10 2006 EN61000 6 2 2005 EN61000 6 4 2001 EN61000 3 2 2005 EN61...

Page 26: ...integrates most functions Max 35 controls in the same bus connection Alarm output Potential free SPDT change over max 48V 0 5A Fault output Potential free SPDT change over max 48V 0 5A Supply output 2...

Reviews: