Fire switches
The fire switch will contain the following:
•
Breakable glass window and red control button, activated by pressure - this puts
the control unit in ALARM status, by which the motor output is activated (for
normal service and testing the lid can be opened with a key).
•
RESET button which brings the control unit out of the alarm status and starts
the closing sequence for about 180 seconds. Please note that RESET does
not cancel errors in the system, e.g. line errors etc. These must be found and
corrected. When a detector is still alive after reset, the control will go immediately
in alarm status again.
•
RED LED indicates that the control unit is in ALARM status and that the motor
output either is or has been activated.
•
YELLOW LED indicates faults on the system - please call for a service
technician.
•
GREEN LED indicates that the system is in normal operation status without
errors.
The master control has an integrated priority fire switch.
Additional connection of the external fire switches are made as shown on the
drawing.
When the control is fully loaded, max. 8 external fire switches can be connected.
When there is no load (Master), max. 10 fire switches can be connected.
The installation with fire switches must be terminated with a resistor (10kΩ -
27kΩ) in the last switch in order to establish the line monitoring correctly – this
can either be done by moving the factory mounted resistor from the terminal
strip to the last fire switch or connect
jumper J1 in the fire switch (by this a
10KΩ resistor is also connected).
By means of DIP switches the control unit has different possibilities of settings
for the input to the fire switch:
DIP 1 (Con.Fire.Sw):
On = ALARM status from 500-3KΩ, (indication of line error by direct short circuit
or open circuit).
Off = ALARM status from 0-3KΩ (indication of line error by open circuit).
DIP 2 (Fail Safe):
On = Any line error on fire switch or smoke detector puts the control unit in
ALARM status. This function can be used if cables to fire switches and smoke
detectors are not fireproof.
Off = An error status does not report ALARM status.
Terminals BVT
1. green LED OK (lights when OK and while closing)
2. yellow LED (lights on error)
3. red LED alarm (emergency opening)
4. ground (-)
5. not used
6. fire switch reset
7. fire switch emergency opening
Jumper J1 must only be set in
the last or only fire switch
Fail.
24V
ALARM
OK 24V
6
4
3
2
1
4
3
2
1
J1
7
6
4
3
2
1
Gn
d
11 12
24V
10
13
7
J1
7
6
FIRE
15
Reset
14
2
1
FAIL SAFE
C
on.
Fi
re
. Sw
DIP NO
OFF
ON
Red LED
Yellow LED
Green LED
2,2
kΩ
2,2
kΩ
10 K
Ω
Last manual control
point
Fit Jumper J1 for line
monitoring
Manual control point.
Break glass (BVT) No. 1
10 K
Ω
Break glass (BVT)
1
Buzzer
3
4
6
7
LED
OK
LED
2
i
LED
Alarm
GND
Reset
24V
24V
Green
Yellow
Red
24V
2,2kΩ
J1
Jumper
10kΩ
Reset
Alarm
doorswitch
FIRESWITCH
SKYCOM CE
10
15
12
11
14
13