SPG 84 Installation manual
5.
Inputs
The panel has 4 input , 8 zones with dual end of line resistors. Each zone type could be configured here.
•
Zone :
The number of inputs. Z1...Z8
ZT is the enclusure tamper pinout. ZA is the AC loss pinout. (Attention ! Its an independent 3V DC input !)
Shortcircuit the input (not the zone) will trigger alarm event from both zones.
•
Zone Types:
−
Disabled:
If disabled is selected, no need to install EOL resistors.
−
Normal:
Immediate zone meaning if the system is Armed, violate
this zone type will activate an alarm immediately.
−
24Hour:
24 hour zone will activate an alarm , regardless if the system is armed or disarmed.
−
Delayed
:
The system will not alarm during exit and entry delay times if delayed zones are violated for the duration of entry or exit time.
All other violation will result alarm.
−
Technical:
Similar operation of 24 hour zone, but it will not trigger a Fire or Alarm message. Its to be used if any sort of contact
information is to be transmitted regardless if armed or disarmed status. EG, temperature sensor, pump or other device
activation e.t.c.
−
Follower:
A „Follower” zone will act as an „Normal” zone if it has been triggered by itself. If a handover zone has triggered after a
„Delay” zone, the remaning delay time will handower from the delay zone to the handower zone.
-
Stay:
Same as Normal type zone, but in Stay arming it will be bypassed automatically in Stay mode arming. If during exit time
the Delayed zone is violated than this zone will be handled as Normal zone type. If Delayed zone is not violated during exit
time that this zone will be shunted when exit time cycle is expired.
−
24h Fire:
Similar operation of 24 hour zone, but it will trigger a Fire Alarm message.
−
24h Fire trouble:
Similar operation of 24 hour zone, but it will trigger a Fire Alarm Trouble message.
Factory default: all disabled