DA 3800 Flange Inlet
26
Mounting Guide
3.5.3 Spring unit on pull rod
The differential switch on the flap and frame must be
set (click) to standard opening before pulling the spring
unit. Perhaps see section
Position of the differential switch on the flap.
The positioning of the differential switch on the frame
(factory setting)
The actuator that opens and closes the inlet must be in
the home position, and the inlet must be closed.
Mount the clip on the spring unit.
Mount the spring unit incl. clip on the pull rod.
Pull the spring unit until the scale shows
1
for standard
opening and
6
for differential opening.
Screw the spring unit onto the pull rod, the screw must
be tightened with 3 Nm.