Servicing
User Manual
SKOPE Pegasus Vertical Freezer - Integral
Troubleshooting
Complaint
Possible Cause
Repair
1. Cabinet not
operating and
no controller
display:
• Loss of power supply.
• Check mains power supply.
2. Cabinet lights
not operating:
• Failed LED light tube.
• Replace LED light tube (see
page 14).
• Controller high temperature
shutdown alarm ‘CHt’.
• Determine cause and
eliminate (see ppage 10).
• Cabinet ENSTO supply plug
not plugged into control box.
• Reconnect plug.
3. Power
consumption
is higher than
expected:
• Unit operating too hot.
• Clean condenser. Ensure
the chiller is installed with
good ventilation above the
refrigeration unit.
• Cabinet doors are opened
excessively.
• Keep door/s open for
minimum time.
4. Product is too
warm and
spoiling:
• Restricted cabinet airflow.
• Ensure product is not
blocking airflow slots and the
product is no closer than
50mm from the cabinet top.
• Temperature setpoint is too
warm.
• Adjust setpoint (see
page 10).
5. Warm cabinet
temperatures
and/or
compressor
operating for
long periods
(more than 1
hour):
• Blocked condenser.
• Clean condenser (see
page 15).
• Poor refrigeration unit
ventilation.
• Ensure the cabinet is
installed with good
ventilation around the front
of the refrigeration unit (see
page 6).