TROUBLESHOOTING THE C-LEVEL
™
SENSOR
1. Verify that the black tube is not kinked or has any holes in it. If either condition exists, the pressure sensor may fail or give
inaccurate level readings.
2. Vent must be above water and unobstructed. This is required to compensate for barometric pressure changes. Obstructing
the vent will result in inaccurate level readings.
3. The black diaphragm is located on the end of the sensor body. The diaphragm must not be damaged or deformed. A damaged
or deformed diaphragm will result in inaccurate level readings.
4. Verify the bottom of the C-Level
™
sensor is not resting on the bottom of the tank or on any other obstacle.
5. Verify that the electrical cable is not damaged or severed.
6. Verify that the shielding for cable is properly connected to the terminal block.
7. Verify that the C-Level
™
sensor is properly connected to the terminal block.
TESTING THE SJE LEVEL MONITOR
™
CL
The SJE Level Monitor
™
CL alarm can be tested by pressing the "Test/Silence" button. This can only be done when the unit is not
in alarm mode. The "Test/Silence" button will activate the audible alarm, alarm LED light, and auxiliary contacts.
Note:
"Test" button only test to insure the audible alarm, visual alarm, and auxiliary contacts are working. "Test/Silence" button
does not test set points. To test set points, fill and empty the tank to insure proper operations.