TROUBLESHOOTING THE  C-LEVEL

 SENSOR

1.   Verify that the black tube is not kinked or has any holes in it. If either condition exists, the pressure sensor may fail or give 

inaccurate level readings.

2.  Vent must be above water and unobstructed. This is required to compensate for barometric pressure changes. Obstructing 

the vent will result in inaccurate level readings.

3.  The black diaphragm is located on the end of the sensor body. The diaphragm must not be damaged or deformed. A damaged 

or deformed diaphragm will result in inaccurate level readings.

4.  Verify the bottom of the C-Level

 sensor is not resting on the bottom of the tank or on any other obstacle.

5.  Verify that the electrical cable is not damaged or severed.

6.  Verify that the shielding for cable is properly connected to the terminal block.

7.  Verify that the C-Level

 sensor is properly connected to the terminal block.

  

TESTING THE SJE LEVEL MONITOR

 CL

The SJE Level Monitor

 CL alarm can be tested by pressing the "Test/Silence" button. This can only be done when the unit is not 

in alarm mode. The "Test/Silence" button will activate the audible alarm, alarm LED light, and auxiliary contacts.

Note:

 "Test" button only test to insure the audible alarm, visual alarm, and auxiliary contacts are working. "Test/Silence" button 

does not test set points. To test set points, fill and empty the tank to insure proper operations.