3.    To change the SJE Level Monitor

 CL monitoring level, push the "Set" button. This will toggle the light bar up one position.

4.  After desired monitoring level is lit, wait 10 seconds and the SJE Level Monitor

 CL will return to normal operating mode.

 

Note:

 During alarm set point mode, if at any time a button is not pushed within 10 seconds the unit will return to normal 

operating mode.

5.   Functionally test system each time alarm is set to insure system is operating as expected.

 

 SILENCING THE SJE LEVEL MONITOR

 CL

The SJE Level Monitor

 CL has two alarm modes available: 

Temporary Silence Mode

 and 

Complete Silence Mode

Temporary Silence Mode

 will silence an active alarm. When pressing the "Silence/Test" button during an active alarm the unit will 

silence the audible alarm but will still leave the auxiliary contacts and LED activated. When the liquid level falls out of alarm level 

for 5 seconds, the audible alarm will reset.

Complete Silence Mode

 disables the audible alarm of the monitor but will still leave the auxiliary contacts and alarm LED 

enabled. When the monitor is set up in this mode, when the alarm level is reached, contacts will activate and the LED will light 

up but no audible alarm will be active. To set the monitor in 

Complete Silence Mode

 perform the following steps:

1.   Disconnect power to the SJE Level Monitor

 CL and any product connected to auxiliary contacts as shown in 

Figure G

.

2.  Disconnect terminal block.

3.  Remove four corner screws on the front cover.

4.  Turn cover over to view the back as shown in 

Figure H

. Move jumper of J5 from pin 1 and pin 2 for audible alarm mode to pin 

2 and pin 3 for complete silence mode.

5.  Reassemble alarm and reconnect terminal block.

6.  Connect power and test alarm to ensure system operates properly.

The alarm can also be disabled. See "SET AND CHECK THE ALARM LEVEL" section under "Alarm Set Points Mode". When alarm is 

disabled, the monitor will not activate the audible alarm, alarm LED, or auxiliary contacts.

Figure G

Figure H