* MODBUS CONNECTION DIAGRAM

1

2

0

 O

h

m

120 Ohm

Master

Slave - 1

Up to 127 slave devices 
can be controlled.

Slave - 2

Slave - 127

A

B

A

B

A

B

A

B

Termination  should  be  accomplished  by 
attaching  120  Ohm  resistors  to  the  start 
and at the end of the communication line.

*  Applies to devices with Modbus function.

51mm

8

0

m

m

 45     mm

 4

5

  

  

 m

m

87mm

Swich

+

CONNECTION DIAGRAM

ENDA ET4430

 PID Temperature Controllers are intended for installation in control panels. Make sure that the device is used only for intended 

purpose. The shielding must be grounded on the instrument side. During an installation, all of the cables that are connected to the device must 
be  free  of  energy. The  device  must  be  protected  against  inadmissible  humidity,  vibrations,  severe  soiling.  Make  sure  that  the  operation 
temperature is not exceeded. All input and output lines that are not connected to the supply network must be laid out as shielded and twisted 
cables. These cables should not be close to the power cables or components. The installation and electrical connections must be carried on by 
a qualified staff and must be according to the relevant locally applicable regulations.

Check  carefully  sensor  pinouts 
a n d   t e r m i n a l   s i g n s   b e f o r e  
connecting the device.
(PT100 sensor connection may be 
irrespective of polarity)

2

1

1

2

TC

-

-

+

9

10

8

9

10

PT100

DIMENSIONS

Depth

 

 -

  

While pressing both side of the device 

in direction

    

 

   and 

push it in direction 

     

 

.

To

 removing the device from

 

the panel

 

:

1

2

Connection

Cables

PANEL CUT-OUT

Flush 

mounting

clamp

Panel

Note :

1)

 While panel mounting, additional distance required for 

connection cables should be considered.

2

Panel  thickness  should  be  9mm

  maximum.

3)

 

  

If there is no free space at back side of 

 

the device,

 

it 

would  be  difficult  to  remove  it  from  the  panel.

  100mm 

clearance should be left behind the device.

NOTE :

SUPPLY VOLTAGE 

184-253V AC

or

21.6-26.4V AC

50/60Hz 5VA

Line

Neutral

12

11

F 100 mA 250V AC

Fuse should
be connected.

Supply

230V AC or 24V AC

Cable Size 

: 1,5mm²

SENSOR  INPUT:
For Thermocouples :

Use  the  correct  compensating  cable.  Do  not  make 
a n y   s u p p l e m e n t   t o   c a b l e s .   C o n n e c t   t h e  
thermocouple cables to the right places at the input 
terminal.

For resistance (PT100) Sensor : 
In order to using 2-wire resistance sensors (PT100), 
8th and 9th terminals must be short circuited. Please 
check connection diagrams carefully.

Holding screw

 0.4-0.5Nm. 

Equipment is protected 

throughout by 

DOUBLE INSULATION

Logic output of the instrument is not electrically 
insulated  from  the  internal  circuits.  Therefore, 
when using a grounding thermocouple, do not 
connect the logic output terminals to the ground. 

1)

  Mains  supply  cords  shall  meet  the 

requirements of  IEC 60227 or IEC 60245. 

2)

 In accordance with the safety regulations, the 

power supply switch shall bring the identification 
of the relevant instrument and it should be easily 
accessible by the operator.

Note

 :

Please see ET4430 Series Modbus Address Map and 
Connection Diagram Guide for Modbus feature.

SİSEL MÜHENDİSLİK ELEKTRONİK SAN. VE TİC. A.Ş.

Şerifali Mah. 

 Y.Dudullu  34775

ÜMRANİYE/İSTANBUL-TURKEY
Tel : +90 216 499 46 64 Pbx.    Fax : +90 216 365 74 01
url : www.enda.com.tr

Barbaros Cad. No:18

 

2

/4

5

8

m

m

4

8

m

m

TEMPERATURE CONTROLLER

ET4430

     

SSR

F

E

T

44

3

0-230VAC 

P

ID TEMPERATURE

 CONTROLLER

SSR
OUT

DIN


-

-

+

TC

PT100

ENDA

SN: XXXXXXXXX

MADE IN TURKEY

1

2

3

4

5

6

7

8

9

10

8 680407 724215

OUT1

OUT2

AC 250V 

10

A

RESISTIVE
LOAD

AC 250V 

5

A

RESISTIVE
LOAD

11

12

13

16

14

15

17

90-

2

5

0V AC 

50/60Hz  5VA

 

INDUSTRIAL
ELECTRONICS

E

T

44

3

0-230VAC

-RS

 

P

ID TEMPERATURE

 CONTROLLER

SSR
OUT

DIN


-

-

+

TC

PT100

-

+

RS- 485

A

B

RS-485 COM.

8 680407 724222

INDUSTRIAL
ELECTRONICS

ENDA

SN: XXXXXXXXX

MADE IN TURKEY

1

2

3

4

5

6

7

8

9

10

OUT1

OUT2

AC 250V 

10

A

RESISTIVE
LOAD

AC 250V 

5

A

RESISTIVE
LOAD

11

12

13

16

14

15

17

90-

2

5

0V AC 

50/60Hz  5VA

 

E

T

44

3

0-2

4

VAC 

P

ID TEMPERATURE

 CONTROLLER

SSR
OUT

DIN


-

-

+

TC

PT100

ENDA

SN: XXXXXXXXX

MADE IN TURKEY

1

2

3

4

5

6

7

8

9

10

8 680407 724253

OUT1

OUT2

AC 250V 

10

A

RESISTIVE
LOAD

AC 250V 

5

A

RESISTIVE
LOAD

11

12

13

16

14

15

17

INDUSTRIAL
ELECTRONICS

2

4

V AC ±10%

50/60Hz  5VA

 

E

T

44

3

0-2

4

VAC

-RS

 

P

ID TEMPERATURE 

CONTROLLER

SSR
OUT

DIN


-

-

+

TC

PT100

-

+

RS- 485

A

B

RS-485 COM.

8 680407 724260

INDUSTRIAL
ELECTRONICS

ENDA

SN: XXXXXXXXX

MADE IN TURKEY

1

2

3

4

5

6

7

8

9

10

OUT1

OUT2

AC 250V 

10

A

RESISTIVE
LOAD

AC 250V 

5

A

RESISTIVE
LOAD

11

12

13

16

14

15

17

2

4

V AC ±10%

50/60Hz  5VA

 

ET4430-EN-01-190116

ENDA

TM

Summary of Contents for ENDA ET4430

Page 1: ...screw terminal connections 1 5mm EN 61326 1 2013 Performance criterion B satisfied for EN 61000 4 3 standard EEPROM minimum 10 years Max 100 Ohm EN 61010 1 2010 Pollution degree 2 overvoltage category...

Page 2: ...pplement to cables Connect the thermocouple cables to the right places at the input terminal For resistance PT100 Sensor In order to using 2 wire resistance sensors PT100 8th and 9th terminals must be...

Page 3: ...ent Alarm A1 tp indE Deviation Alarm A1 tp dE Band Alarm A1 tp bAnd SV CONT output set value ASV Alarm output set value ASV min 300 ASV maks 300 ASV min beginning of scale ASV max end of scale ASV min...

Page 4: ...m bAnd Band alarm bAn i Band with inhibition A2s t Status selection for Alarm2 Output If Hi is selected A2 output is above the Alarm2 set value ON If lo is selected A2 Output is above the Alarm2 set v...

Page 5: ...rm 2 Band alarm 3 Active alarm after in band time ModBus device address Adjustable between 1 and 247 Modbus communication speed Baudrate 0 Modbus cancel 1 2400 bps 2 4800 bps 3 9600 bps 4 19200 bps 5...

Page 6: ...d 002Dh 0047d 002Fh 0048d 0030h 0049d 0031h 0050d 0032h 0051d 0033h 0052d 0034h 0041d 0029h 0042d 002Ah H41 H43 H44 H45 H47 H46 H48 H49 H50 H51 H52 H40 H42 R W R W R W R W R W R W R W R W R W R W R W...

Page 7: ...the query is not an allowable action for the slave If a Poll Program Complete command was issued this code indicates that no program function preceded it The data address received in the query is not...

Reviews: