11
Supervision Device (FSD) is operating
correctly. Always check that the gas has
stopped flowing even if you hear the FSD
valve close within the 3-minute period.
Turn OFF the appliance and the gas supply
and refit the pressure test point sealing screw.
Turn ON the gas supply and check for leaks
around the pressure test point sealing screw
with a suitable leak detection fluid.
8
CHECK FOR SPILLAGE
A SPILLAGE CHECK MUST BE MADE
BEFORE THE INSTALLED APPLIANCE
IS LEFT WITH THE CUSTOMER. DO
THIS TEST WITH ALL THE COALS
FITTED AND THE FENDER AND
ASHPAN IN PLACE. CARRY OUT THE
TEST AS FOLLOWS:
8.1
Close all doors and windows in the room
containing the appliance.
8.2
Light the appliance and set to the HIGH
setting.
8.3
Leave the appliance ON for 5 minutes
then light a smoke match. The match
should be inserted 10mm below the top
of the opening and be pointed upwards
at 45° to the horizontal.
Move the smoke match across the
opening. The installation is satisfactory if
all the smoke is drawn into the chimney.
8.4
If all the smoke is not drawn into the
chimney, leave the fire alight for a further
10 minutes at the HIGH setting and then
repeat the test. If all the smoke is still not
drawn into the chimney, inspect the
sealing to the fireplace surround. If the
sealing is satisfactory DISCONNECT THE
APPLIANCE AND SEEK EXPERT
ADVICE.
8.5
Open all internal connecting doors,
hatches, etc in the same room as the
appliance. Keep all the doors and windows
that open to the outside of the building
closed. Re-check for spillage as described
above. If an extractor fan is fitted in the
same room as the appliance or a
connecting room, check that spillage does
not occur with the fan operating, all doors,
and other openings between the fan and
the appliance open.
9
FINAL CHECK AND CUSTOMER
BREIFING
9.1
Instruct the customer on the full operation
of the appliance.
9.2
Advise the customer how to assemble the
fuel effect as described in these
instructions and that any build up of soot
can be removed as described in
CLEANING on page 4 of these
instructions.
9.3
Advise the customer that any cleaning
MUST be carried out when the appliance
is cold.
9.4
Please explain to the customer the
purpose of the Oxygen Depletion System
(ODS) and in particular the following:
(a)
The ODS system operates if the Oxygen
level in the room falls below safe levels
usually due to interruption of the
evacuation of combustion products i.e. a
blocked chimney etc.
(b)
Describe the restart procedures.
(c)
Point out that on repeated operation of
the ODS system seek expert advice.
9.5
Hand over these instructions to the
customer for keeping in a safe place.
9.6
Recommend that the appliance and
chimney should be inspected and serviced
by a competent person annually.
10
SERVICING
TURN OFF THE GAS SUPPLY AND
A L L O W
T O
C O O L
B E F O R E
COMMENCING ANY SERVICING.
ALWAYS TEST FOR GAS SOUNDNESS
AND SPILLAGE AFTER REFITTING THE
APPLIANCE. (A LONG BRUSH MAY BE
REQUIRED TO REACH SOME JOINTS
FOR SOUNDNESS TESTING.)
Check that the appliance is clean and that soot
deposits or debris is not blocking the gaps
between coals causing an imperfect flame
appearance or that stray pieces of soot are not
impairing the electrode spark or pilot burner.
After servicing, make sure that the fuel effect is
correctly assembled as described on pages 9
– 15.
VII-11-09