background image

23

ENGLISH

11.Repair to intrinsically safe components

Do not apply any permanent inductive or capacitance loads to the circuit with-
out ensuring that this will not exceed the permissible voltage and current per-
mitted for the equipment in use.
Intrinsically safe components are the only types that can be worked on while 
live in the presence of a 

fl

 ammable atmosphere. The test apparatus shall be 

at the correct rating.
Replace components only with parts speci

fi

 ed by the manufacturer. Other parts 

may result in the ignition of refrigerant in the atmosphere from a leak.abling
Check that cabling will not be subject to wear, corrosion, excessive pressure, 
vibration, sharp edges or any other adverse environmental effects. The check 
shall also consider the effects of aging or continual vibration from sources such 
as compressors or fans.

12. Cabling

Check that cabling will not be subject to wear, corrosion, excessive pressure, 
vibration, sharp edges or any other adverse environmental effects. The check 
shall also consider the effects of aging or continual vibration from sources such 
as compressors or fans.

13. Detection of 

fl

 ammable refrigerants

Under no circumstances shall potentially sources of ignition be used in the 
searching for or detection of refrigerant leaks. A halide torch (or any other de-
tector using a naked 

fl

 ame) shall not be used.

14.   Leak detection method

For systems containing 

fl

 ammable refrigerants, the following methods for de-

tecting leaks are acceptable:
Electronic leak detectors can be used for the detection of 

fl

 ammable  refrig-

erants, but the sensitivity may not be suf

fi

 cient or may require recalibration 

(the instrument calibration should be performed in a refrigerant-free environ-
ment) to ensure that the leak detector does not become a potential The ignition 
source, and applies to the measured refrigerant, the leak detector should be 
set to the lowest 

fl

 ammable concentration of the refrigerant (in percent), cali-

brated with the used refrigerant and adjusted to the appropriate gas concentra-
tion test range (max. 25%)
The leak detection 

fl

 uid is suitable for most refrigerants, but do not use oxygen-

Summary of Contents for SDHM-10L SMART OUT

Page 1: ...SDHM 10L SMART OUT Dehumidifier GB INSTRUCTION MANUAL GR R290...

Page 2: ...GB ENGLISH 3 GR E 28...

Page 3: ...fore using and maintenance SYMBOLS FROM THE UNIT AND USER MANUAL This unit uses a flammable refrigerant gas If refrigerant gas leaks and comes in contact to fire or heating part it will be created har...

Page 4: ...ce or burn Do not use means to accelerate the defrosting process or to clean other than those recommended by the manufacturer Compliance with national gas regulations shall be observed Keep ventilatio...

Page 5: ...RMATION Avoid installation behind a door Use only with the supply voltage specified on the rating plate of the Dehumidifier Before installing cleaning and servicing turn off the power and unplug the u...

Page 6: ...ays remove plug from the mains supply before cleaning Switch off the appliance before changing its position Do not remove the power plug from the socket by pulling the cord grip the plug instead Alway...

Page 7: ...avy objects on the appliance Do not cover the intake or exhaust opening with cloths or tow els Do not drink or use the water drained from the unit Do not take the water tank out during operation Empty...

Page 8: ...the machine or injuries to persons or animals 4 In case of manipulation repairing or any modification of the machine made by unqualified persons or in case of improper use the guarantee will be autom...

Page 9: ...90 Rated Input Current 1 25A 27 C 60 Max Rated Input Current 1 40A 32 C 90 Water Tank Capacity 2 2L Air volume 120m h Noise Level 45dB A Refrigerant Charge R290 35 g Product Dimensions LxWxH 280X240X4...

Page 10: ...r the diagram shown below Notes Before moving the unit remove any water from the water tank To save energy keep windows and door closed when unit is running Please install the unit on a flat horizonta...

Page 11: ...utton to set the desired dehumidification degree 30 80 The humidity can be set in 5 increments from 30 35 40 45 80 MODE Press the MODE button to select the mode of operation Four dif ferent modes are...

Page 12: ...ty can be shown on the panel FAN Press the FAN button to select this mode You can switch to low or high fan speed by pressing the FAN button again TIMER Press the button to determine off or on time 0...

Page 13: ...ol panel buttons Press and hold LOCK button again for more than 3sec to unlock all the control panel buttons AIR CLEAN By pressing this button only AIR FILTER mode is in operation Under this mode Dehu...

Page 14: ...ehumidifying mode High Dehumidifying mode Continuous clothes drying mode Room Humidity when the SETTING button is pressed the Set Hu midity is displayed Timer hours Water Tank full Water Tank not plac...

Page 15: ...ated in room temperature less than 18 Defrosting function may start up and operate for some time about 5 minutes automatically every 25 minutes or even longer according to room temperature 18 temperat...

Page 16: ...is dirty clean by cool water or warm water cannot use cleaner steel wool chemical rag duster gas oil benzene thinner or other solvent to clean it otherwise it would damage the water tank and lead to l...

Page 17: ...long its life and keep it functioning properly Warning Before performing any cleaning turn off the unit and unplug it to avoid electrical shocks Do not use hot water or chemical solvents for cleaning...

Page 18: ...uct Loud noise when run ning Is the machine put in the plat place Put the machine on the plat ground Is the filter clogged Wash the filter Stop operation dur ing the dehumidifying process Whether the...

Page 19: ...nventilated space that compliance with national gas regulations shall be observed that mechanical connections shall be accessible for maintenance pur poses that for appliances containing flammable ref...

Page 20: ...ion shall be completed prior to conducting work on the system 2 Work procedure Work shall be undertaken under a controlled procedure to minimize the risk of a flammable gas or vapor being present whil...

Page 21: ...shall continue during the period that the work is carried out The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere 8 Checks to the ref...

Page 22: ...mponents and wiring are exposed while charging recovering or purging the system that there is continuity of earth bonding 10 Repairs to sealed components During repairs to sealed components all electr...

Page 23: ...erse environmental effects The check shall also consider the effects of aging or continual vibration from sources such as compressors or fans 13 Detection of flammable refrigerants Under no circumstan...

Page 24: ...ppliances containing flammable refrigerants the system shall be purged with oxygen free nitrogen to render the appliance safe for flammable refriger ants This process may need to be repeated several t...

Page 25: ...to the task being carried out an oil and refrigerant sample shall be taken in case analysis is required prior to re use of recovered refrigerant It is essential that electrical power sup ply is availa...

Page 26: ...used are designated for the recovered refrigerant and labelled for that re frigerant i e special cylinders for the recovery of refrigerant Cylinders shall be complete with pressure relief valve and as...

Page 27: ...is product shall not be treated as household waste Instead it shall be handed over to the applicable collection point for the recycling of electrical and electronic equipment By ensuring this product...

Page 28: ...28 T R290 R290 ODP GWP R290 R290...

Page 29: ...29 R290 4 m2...

Page 30: ...30...

Page 31: ...31 SINGER...

Page 32: ...32...

Page 33: ...33 1 service 2 SINGER SINGER SINGER...

Page 34: ...34 3 Singer 4 24...

Page 35: ...35 SDHM 10L SMART OUT 10L day 30 C 80 AC220 240V 50Hz 200W 27 C 60 max 245W 32 C 90 1 25A 27 C 60 max 1 40A 32 C 90 2 2L 120m h 45dB A R290 35 g x x 280X240X460 9 5kg 1 2MPa 2 5MPa SILVER...

Page 36: ...36...

Page 37: ...37 3 50 50 70 70 POWER POWER SETTING 30 80 5 5 30 35 40 45 80 MODE MODE...

Page 38: ...38 1 55 RH 2 MODE 3 MODE 4 MODE...

Page 39: ...39 FAN FAN FAN TIMER X 0 24 Timer 1 24 24 1 Timer Timer 5 Timer Timer 5 Timer...

Page 40: ...40 CHILDLOCK LOCK 3 LOCK 3 AIR CLEAN SLEEPMODE Sleep Sleep Sleep...

Page 41: ...41 LED DISPLAY SETTING...

Page 42: ...42 5 20 18 5 25 18 23 120 12 18 25...

Page 43: ...43 5 12 20 1 2 3...

Page 44: ...44 1 2 3 Drying...

Page 45: ...45 SILVER 5 35...

Page 46: ...46 R290 0 236ohm 0 236 ohm...

Page 47: ...47 100m3 h...

Page 48: ...48 1 2 3 4...

Page 49: ...49 5 6 7 8...

Page 50: ...50 9...

Page 51: ...51 10 11...

Page 52: ...52 12 13 14 25 OFN...

Page 53: ...53 15 16...

Page 54: ...54 17 H...

Page 55: ...55 80 18 19...

Page 56: ...56...

Page 57: ...57 SSM EMC Directive 2014 30 EU LVC Low Voltage Directive 2014 35 EU ROHS Directive 2011 65 EU...

Page 58: ...58 NOTES...

Page 59: ...59 NOTES...

Page 60: ...SSM S A 6 KIFISSOU STR 122 42 EGALEO ATHENS GREECE T 30 210 5386400 30 210 5138141 SSM A E 6 122 42 210 5386400 210 5138141 VELANIS APPLIANCES 62 104 43 T 210 5135874 210 5139517 www singer gr...

Reviews: