Sinclair SWH-200IRA2 User Manual Download Page 34

Air Source Heat Pump Water Heater

 

29 

distance  between  them  should  be  greater  than  20  cm.  Otherwise,  the 

unit may not be able to communicate properly. 

(2)  If  the  unit  is  installed  in  a  place  susceptible  to  electromagnetic 

interference, the communications line of the wired controller and the line 

of the temperature sensor must be used, shielded twisted pair. 

10.3 Rainproof Box Installation 

If  the  wired  controller  is  to  be  installed  in  outdoors  or  dank  places,  please 

install  a  rainproof  box  for  wired  controller.  Pay  attention  to  cut  off  the  power 

supply of heavy current wire embedded in the installation hole of wall. The whole 

installation procedure shall be done without electricity. The installation method is 

as follows: 

Separate the panel of wired control and bottom plate with a flat screwdriver; 

Pull  out  the  communication  wire  (4-core  twisted  pair  wire)  inside  the 

installation box and make this wire go through the wire-crossing hole of rainproof 

box and wired controller bottom plate; 

Secure the bottom plate of wired controller, rubber cushion, rainproof box at 

the installation box with screws; if there is no installation box in the wall, please 

drill hole on the wall and install plastic expansion pipe. Secure the bottom plate of 

wired controller, rubber cushion and rainproof box at the plastic expansion pipe 

with tapping screws (plastic expansion pipe and tapping screw are provided by 

our company); 

Insert the communication cable (4-core twisted pair wire) into the groove of 

wired controller; 

Align  the  panel  of  wired  controller  with  the  bottom  plate  and  then  fasten 

them together. 

Note:  When  disassembling  the  wired  controller,  please  use  the  flat 

screwdriver carefully (As shown in Figure 10-4). 

Summary of Contents for SWH-200IRA2

Page 1: ...SWH 200IRA2 SWH 35ERA2 SINCLAIR WATER HEATER USER S MANUAL EN P U M P S H E A T...

Page 2: ...ply please energize and preheat the unit in advance before reusing it 3 Please properly select the model according to actual the using environment otherwise it may impact the using convenience 4 This...

Page 3: ...or use the product with other equipment without abiding by the instruction manual of manufacturer 3 After verification the defect of product is directly caused by corrosive gas 4 during operation impr...

Page 4: ...4 7 Pipeline Connection 15 7 1 Refrigerant Pipe Connection 15 7 2 Exhaust Methods 17 7 3 Water Pipe Connection 19 8 Installation Diagram of the Unit 23 9 Wiring 24 9 1 Wire Layout 24 9 2 Wire Connecti...

Page 5: ...age of Water Tank 38 16 2 Periodic Cleaning for Water Tank 38 16 3 Replacement of magnesium rod 39 16 4 Safety Valve Maintenance 40 16 5 Maintenance of the Unit 41 17 Precautions for Safety Usage 41 1...

Page 6: ...heater is a thermal storage water heater The user shall open the cold water valve first then adjusting cold and hot water flow to proper water temperature gradually to avoid scald injury If not using...

Page 7: ...5 Be sure to pull out the power plug and drain the main unit and water tank when water heater is not in use for a long time Otherwise the accumulated dust may cause overheating fire or freeze of water...

Page 8: ...ger Never put your hands at the air outlet of the unit 12 Do not repair the unit by yourself in case of electric shocks or fire hazards Please contact the SINCLAIR appointed service center 13 Do not s...

Page 9: ...unit for startup otherwise it might damage the unit or result in fire hazard 19 It is highly recommended to place the unit where good ventilation is available 20 Check the safety relief valve for blo...

Page 10: ...product should not be disposed with other household wastes throughout the EU To prevent possible harm to the environment or human health from uncontrolled waste disposal recycle it possibly to promot...

Page 11: ...gerant pipe and a water pipe It provides hot water to users for household use The appearance of the main parts is shown in Figure 2 1 Actually the appearance of the product may not be exactly the same...

Page 12: ...Rated Input Power W 833 360 910 COP W W 4 10 Load Profile L COPDHW W W 3 10 Energy Efficiency Class 2 A Water Heating Energy Efficiency 2 130 Annual electricity consumption average climate conditions...

Page 13: ...85 Power Supply for Electric Heater 220V 240V 50Hz Input Power for Electric Heater W 1500 Outline Dimensions W x D x H mm 462 x 462 x 1944 Package Dimensions W x D x H mm 583 x 583 x 2045 Water Tank G...

Page 14: ...transfers the heat to a condenser through a compressor and releases it to the water inside the water tank In this way the water is heated up The working principles of an air source water heater are th...

Page 15: ...ank to enhance heat transfer In testing conditions of the unit the coefficient of performance COP reaches up to 3 0 and the operating costs are more economical than conventional heaters 2 Reliability...

Page 16: ...ur local service centers authorized by Sinclair In the case of anair source water heater installed by any party not authorized or designated by Sinclair Sinclair shall not undertake any responsibility...

Page 17: ...ust be installed at a location where 1 The noise and air flow generated by the air outlet do not affect neighbors animals and plants 2 Good ventilation of the main unit can be ensured and there are no...

Page 18: ...1 Dimension diagram of the main unit structure 2 The distance between the main unit and the walls or other obstructions must not be too small and the space for installing the main units must meet the...

Page 19: ...mouth and guide the drainage pipe to a proper place for drain Outdoor unit chassis Outdoor unit drainage joint Figure 5 3 Drainage pipe connection 6 Installation of the Water Tank 1 The water tank can...

Page 20: ...plenishment for the water tank hot water supply and drainage And the pressure of the tap water shouldn t higher than 0 7MPa else a decompressor should be installed in the water inlet pipe 7 Pipeline C...

Page 21: ...rigerant oil on the joint and valve cones 4 Remove the sealing caps of the connecting pipe Align the center of the bell mouth with the pipe joint and valve cone and screw up the conical nut with your...

Page 22: ...t needs to be extended 1 Use a refrigerant in the outdoor unit 1 Remove the valve cap and the fluoride injection mouth nut from the fluid valve and the air valve 2 Use a hex key to slightly unscrew th...

Page 23: ...lve Ensure that the valve cores of the air valve and fluid valve are tightly closed 2 Connect the joint of the filling hose to the vacuum pump as shown in Figure 7 4 3 Fully open the low pressure valv...

Page 24: ...not suggested 2 Water inlet and outlet pipe installation Water inlet pipe shall install safety valve filter and cut off valve installation sequence shall accord with unit installation diagram Water ou...

Page 25: ...ressure is too high not over 0 7MPa If water pressure is higher than 0 7MPa install stabilizing valve correctly according to 6 Stabilizing valve installation if water pressure is below 0 7MPa please c...

Page 26: ...e installed in places with temperature below 0 to avoid the pipeline getting frozen due to bad insulation of water system pipeline antifreezing tracing belt for pipeline shall be installed in water in...

Page 27: ...e water safety the PPR pipe length at the water inlet and outlet is determined as per the formula L 70 R2 wherein L indicate the pipe length and R indicates the inner diameter of the pipe unit cm The...

Page 28: ...according to the preceding dimensions and specifications If the cut off valve is installed outdoors PPR pipes are recommended to prevent freezing caused by low temperature Install the piping system on...

Page 29: ...ce on all poles meets the disconnection requirements under overvoltage category III conditions 3 Ensure that reliable grounding measures are taken A dedicated grounding apparatus should be used 4 Use...

Page 30: ...um Sectional Area mm 2 of Power Cables Air Circuit Breaker Capacity A Firing Line Zero Line Groun d Line SWH 35ERA2 220 240V 50Hz 1 5 1 5 1 5 16 9 2 Wire Connections 1 Unscrew the screw on the connect...

Page 31: ...perature sensor Put the temperature sensor inside the connection box The line of the temperature sensor must be clamped tightly Check whether the temperature sensor is securely fastened The interface...

Page 32: ...stall the unit or wired controlled of the air source water heater in a place susceptible to electromagnetic interference 3 Ensure that the communications line is connected to the correct interface Oth...

Page 33: ...munication cable 4 core twisted pair wire in the base box and then make the communication cable go through the hole of soleplate of wired controller Joint the controller s soleplate and base box with...

Page 34: ...control and bottom plate with a flat screwdriver Pull out the communication wire 4 core twisted pair wire inside the installation box and make this wire go through the wire crossing hole of rainproof...

Page 35: ...Assy of Wired Controller No Name No Name 1 Panel of wired controller 4 Rubber cushion rainproof box 2 Screw 5 Rainproof box 3 Bottom plate of wired controller 6 Installation box inside the wall Figure...

Page 36: ...ate The unit may become faulty or the parts may be burnt Does the wire model comply with specifications The unit may become faulty or the parts may be burnt Is a safety check valve installed for the w...

Page 37: ...ntroller has a power memory function However if the wired controller is power on for the first time it may indicate power on power off or standby Note that the unit can be powered on only after the wa...

Page 38: ...to enter the query status When the temperature display area displays 00 press and hold MODE for 5 seconds Then 00 changes to P0 Press the or button to switch to the P3 Then press the MODE button for...

Page 39: ...ay area displays 00 press and hold MODE for 5 seconds Then 00 changes to P0 Press the or button to switch to the P3 Then press the MODE button for settings Press the or button again to change 00 in th...

Page 40: ...with the change of ambient temperature only for reference The unit s water generation capacity will increase with the increased of ambient temperature Under the same ambient temperature the maximum w...

Page 41: ...ove the heating effect 2 When defrosting runs the unit stops running the fan 3 If defrosting runs in high ambient temperatures 10 C the unit is running improperly In this case please report for repair...

Page 42: ...when the outdoor temperature is quite low in winter otherwise the automatic antifreeze protection will fail to work Under low ambient temperature anti freezing operation function of the unit will con...

Page 43: ...ss for water input on the water tank 1 Cut off the power supply and open the cut off valve at the water inlet of the tap faucet 2 Open the cut off valve at the hot water drain outlet and valve in user...

Page 44: ...er input operation 7 Water tank cleaning completed and energize it 16 3 Mg Stick Replacement To improve durability of the water tank a Mg Stick is installed inside the water tank Generally the Mg Stic...

Page 45: ...tion occurs and abnormal noise is caused contact Sinclair authorized maintenance centers The possible causes of this problem are as follows The safety valve is damaged the waterreplenishment pressure...

Page 46: ...bar is necessary Customer can contact Sinclair serviceman for replacement Recommended replace period is 2 3 years 4 Cut off the power supply prior to any maintenance or services A unprofessional pers...

Page 47: ...otherwise it would lead to electric shocks or fire hazards Instead please contact the Sinclair appointed service center and it is better to check the items listed in the table below at first Table 18...

Page 48: ...The water heater stops operation and the wired controller displaysC5 Malfunction of jumper cap The water heater stops operation and the wired controller displays E4 Discharge protection The water heat...

Page 49: ...r displays P0 Drive module reset of inverter compressor The water heater stops operation and the wired controller displays P5 Overcurrent protection of inverter compressor The water heater stops opera...

Page 50: ...The water heater stops operation and the wired controller displays AC Failure startup of inverter outdoor fan The water heater stops operation and the wired controller displays Ad Phase lacking protec...

Page 51: ...d the wired controller displays Ar Malfunction of temperature sensor of drive electric box of inverter fan The water heater stops operation and the wired controller displays U9 Zero crossing protectio...

Page 52: ...containing fluorinated gases included in the Kyoto protocol The maintenance and the liquidation must be carried out by qualified personnel Type of refrigerant R410A The composition of the cooling med...

Reviews: