8.6.9 Installation of multi-module water system pipeline
CAUTION
Cooling capacity
15≤Q≤30
30
<
Q≤90
90
<
Q≤130
130
<
Q≤210
210
<
Q≤325
325
<
Q≤510
510
<
Q≤740
740
<
Q≤1300
1300
<
Q≤2080
Total inlet and outlet water pipe inside nominal diameter
DN40
DN50
DN65
DN80
DN100
DN125
DN150
DN200
DN250
Table 8-10
Multi-module combination installation involves special design of the unit, so relevant explanation is given as follows.
1) Installation mode of multi-module combination water system pipeline
2) Table of diameter parameters of main inlet and outlet pipes
2) Applicable standard of water quality for the unit
PH value
Total hardness
Conductivity
Sulfide ion
Chloride ion
Ammonia ion
Sulfate
Silicon
Iron content
Sodium ion
Calcium ion
/
6.8~8.0
<70ppm
<200μV/cm(25°C)
No
<50ppm
No
<50ppm
<30ppm
<0.3ppm
No requirement
<50ppm
/
Table 8-9
Please pay attention to the following items when installing multiple modules:
- Each module corresponds to an address code which cannot be repeated.
- Main water outlet temperature sensing bulb, target flow controller and auxiliary electric heater are under control of
the main module.
- One wired controller and one target flow controller are required and connected on the main module.
- The unit can be started up through the wired controller only after all addresses are set and the aforementioned
items are determined. The wired controller is ≤500m away from the outdoor unit.
No.n module
No. (n-1)address
No.1 module
No.0 address
No.(n-1) module
No.(n-2) address
Pump
Drill dead hole at the position,
and move the total euent
temperature sensor at No.0
address to the position
Fig.8-24 Installation of multi-module (no more than 16 modules)
27
Summary of Contents for SCV EB Series
Page 1: ...AIR COOLED CHILLER UNIT INSTALLATION AND USER MANUAL SCV XXX B AIR CONDITIONING...
Page 2: ...Original instructions...
Page 3: ......
Page 49: ......
Page 50: ...NOTE 44...
Page 51: ......
Page 52: ...0 1 234 56 0 7 8 234 0 9 1 7 1 0 6 16 3 5 9 4 260 88 4 260 88 08 88 688 0 4 08 4 6 4A8 60 B...