- 24 -
Errors displayed in the
DD
position
P5
01
-
Compressor overcurrent protection
02
-
Power supply protection
04
-
Circuit current measurement malfunction
H7
08
-
Compressor desynchronization protection
10
-
Compressor stalling protection
20
-
40
-
Drive unit module high-temperature protection
80
-
Drive unit module sensor malfunction
In addition to the above errors, the unit automatically checks each parameter setting whether
the set values are within the allowed range. When attempting to write lower than the
permitted value, the error message
Err.min
appears on the first line of the display and the
minimum permitted value of the set parameter is displayed on the second line. Similarly,
when attempting to write higher than the permitted value, the error message
Err.max
appears on the first line of the display and the maximum permitted value of the set parameter
is displayed on the second line.
The error codes E1-P5 are displayed on the digital display of the main board of the outdoor
unit ASGE-xxBI and ASGE-xxBI-3.
7. TECHNICAL PARAMETERS
Supply voltage range:
230V/50Hz ±10%
Maximum input power:
15VA
Net dimensions (W x D x H): 70 x 58 x 90 mm
Net weight:
210 g
Operating temperature:
0°C to +55°C
Storage temperature:
-25°C to +70°C
Inputs:
2 x digital input with TTL levels
2 x input for temperature sensors Carel NTC015WF00, 10kΩ ß
= 3435
1 x voltage input 0-10V with input resistance of 100kΩ
1 x current input 4-20mA for pressure sensor 0-18bar Alco
Controls PT5-18M
Outputs:
3 x relay with NO (normally open) contact, max. 230V/2A
Communication:
Serial communication for controlling the outdoor unit, combined
with the power supply of the outdoor unit communication circuits
(about 18-22V/100mA).
Service connector:
USB, Mini-B connector
Warning:
It is not possible to use an ordinary USB to RS485
converter to monitor the communication between the
indoor and outdoor units because of alternation (time-
division multiplexing) between the serial communication
data signal and the supply voltage of up to 22V (used to
supply the communication circuits of the outdoor unit) on
the SC-1 & SC-2 terminals of the SCMI-01.4 module.
8. CONTENTS OF PACKAGING
SCMI-01.4 communication module
1pc
Temperature sensor
2pc
Instruction manual
1pc
Summary of the SCMI-01.4 module settings