![Sinclair SCMI-01.4 User Manual Download Page 25](http://html1.mh-extra.com/html/sinclair/scmi-01-4/scmi-01-4_user-manual_1280265025.webp)
- 23 -
6.2. Outdoor Unit Errors
Current errors of the outdoor unit are displayed in the last position of the main menu of the
SCMI-01.4 module. The first line contains the title
Error
and the second line contains four
two-digit hexadecimal error codes (or the sum of these codes, if multiple errors occur). After
eliminating the displayed errors, this item will cease to be displayed. To view already not
displayed errors, you should press
ESC
and
ENTER
keys simultaneously, when the default
screen of the SCMI-01.4 module is displayed. You must press these keys in the given order,
i.e. first press and hold
ESC
key and then press also the
ENTER
key. The display shows:
Err -1
AABBCCDD
The number –
1
after the title
Error
identifies the last (previous) error and the second line is
the same as when displaying the current error, i.e. four two-digit hexadecimal error codes (or
the sum of these codes, if multiple errors occur). You can use the ▼/▲ keys to display other
previous errors with numbers from
–2
to
–8
, i.e. it is possible to display up to eight previous
errors. If the number of errors stored in the SCMI-01.4 module memory is lower than 8,
horizontal dashes will be displayed instead of error codes in the empty positions. If the
number of previous errors exceeds 8, all stored error records are shifted and the oldest one
is deleted. In this way, the error list is updated whenever a new error occurs and it cannot be
deleted nor changed by another way. Summary of errors is given in the following tables:
Errors displayed in the
AA
position
E4
01
-
Compressor discharge high-temperature protection
02
-
Lack of refrigerant protection
04
-
Fan DC motor protection
08
-
4-way valve protection
10
-
Overcurrent protection
H3
20
-
Overload protection
E3
40
-
Compressor low pressure protection
E1
80
-
Compressor high pressure protection
Errors displayed in the
BB
position
01
-
Indoor unit freezing protection
F3
02
-
Outdoor ambient temperature sensor malfunction
F4
04
-
Discharge temperature sensor malfunction
F2
08
-
Condenser temperature sensor malfunction
10
-
Condenser inlet tube temperature sensor malfunction
C5
20
-
Invalid power code (invalid position of the jumper)
40
-
Drive unit memory chip malfunction
80
-
Errors displayed in the
CC
position
01
-
Protection against starting compressor at a low frequency at a low voltage
02
-
DC Bus overvoltage protection
04
-
AC current protection
08
-
IPM protection
10
-
PFC protection
20
-
Start up malfunction
40
-
Compressor wrong phase order protection
80
-
Drive unit module sensor malfunction