All the work men who are engaging in the refrigeration system should bear the
valid certification awarded by the authoritative organization and the qualification
for dealing with the refrigeration system recognized by this industry. If it needs
other technician to maintain and repair the appliance, they should be supervised
by the person who bears the qualification for using the flammable refrigerant.
It can only be repaired by the method suggested by the equipment’s manufacturer.
Qualification requirement for installation and maintenance man
Installation notes
The air conditioner is not allowed to use in a room that has running fire (such as fire
source, working coal gas ware, operating heater).
Maintenance notes
Welding
Check whether the maintenance area or the room area meet the requirement of the nameplate.
- It’s only allowed to be operated in the rooms that meet the requirement of the
Check whether the maintenance area is well-ventilated.
- The continuous ventilation status should be kept during the operation process.
Check whether there is fire source or potential fire source in the maintenance area.
- The naked flame is prohibited in the maintenance area; and the “no smoking”
warning board should be hanged.
nameplate.
Check whether the appliance mark is in good condition.
- Replace the vague or damaged warning mark.
If you should cut or weld the refrigerant system pipes in the process of maintaining,
please follow the steps as below:
It is not allowed to drill hole or burn the connection pipe.
The air conditioner must be installed in a room that is larger than the minimum room
area. The minimum room area is shown on the nameplate or following table a.
Leak test is a must after installation.
table a - Minimum room area ( m )
2
Charge amount (kg) ≤1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2 2.1 2.2 2.3 2.4 2.5
4
4
4
4 14.5 16.8 19.3 22 24.8 27.8 31 34.3 37.8 41.5 45.4 49.4 53.6
5.2 6.1
7 7.9 8.9 10 11.2 12.4 13.6 15 16.3 17.8 19.3
4.2 4.6
5 5.5
6
4
4
4
4
4
floor location
wall mounted
window mounted
ceiling mounted
Minimum
room
2
area( m )
Safety operation of flammable refrigerant
Filling the refrigerant
Safety instructions for transportation and storage
a. Shut down the unit and cut power supply
b. Eliminate the refrigerant
c. Vacuuming
d. Clean it with N2 gas
e. Cutting or welding
f. Carry back to the service spot for welding
The refrigerant should be recycled into the specialized storage tank.
Make sure that there isn’t any naked flame near the outlet of the vacuum pump
and it’s well-ventilated.
Use the refrigerant filling appliances specialized for R32. Make sure that different
kinds of refrigerant won’t contaminate with each other.
After filling is finished, please do the leakage detection before test running; another
time of leak detection should be done when it’s removed.
Please use the flammable gas detector to check before unload and open the container.
No fire source and smoking.
According to the local rules and laws.
The refrigerant tank should be kept upright at the time of filling refrigerant.
Stick the label on the system after filling is finished (or haven’t finished).
Don’t overfilling.
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
Summary of Contents for MULTI VARIABLE SERIES
Page 1: ...MULTI VARIABLE SERIES DUCT MV DxxBI SERVICE MANUAL EN ...
Page 13: ...11 Service Manual AUTO COOL DRY FAN HEAT ...
Page 14: ...12 Service Manual horizontal louvers stops at current position no display no display ...
Page 15: ...13 Service Manual Sketch map for replacing batteries ...
Page 18: ...16 Service Manual 6 3 Wired Remote Controller XK19 ...
Page 19: ...17 Service Manual ...
Page 20: ...18 Service Manual ...
Page 21: ...19 Service Manual ...
Page 22: ...20 Service Manual ...
Page 23: ...21 Service Manual memmorizing memmorizing ...
Page 24: ...22 Service Manual ...
Page 25: ...23 Service Manual ...
Page 26: ...24 Service Manual ...
Page 28: ...26 Service Manual 09 12K 18K 24K 7 1 4 7 1 5 ...
Page 29: ...27 Service Manual 7 1 6 ...
Page 30: ...28 Service Manual 7 1 7 7 1 8 ...
Page 31: ...29 Service Manual ...
Page 32: ...30 Service Manual 7 1 9 7 1 10 ...
Page 33: ...31 Service Manual 7 1 11 7 1 12 ...
Page 34: ...32 Service Manual 7 1 13 ...
Page 45: ...PARTS GUIDE MV D09BI MV D12BI MV D18BI MV D24BI DUCT MULTI VARIABLE SERIES 103 ...
Page 46: ...MV D09BI ...
Page 48: ...MV D12BI ...
Page 50: ...MV D18BI ...
Page 52: ...MV D24BI ...
Page 54: ......