14
Service Manual
6.2 Brief Description of Modes and Functions
1.Basic function of system
(1)Cooling mode
(1) Under this mode, fan and swing operates at setting status. Temperature setting range is 16~30ºC.
(2) During malfunction of outdoor unit or the unit is stopped because of protection, indoor unit keeps original operation status.
(2)Drying mode
(1) Under this mode, fan operates at low speed and swing operates at setting status. Temperature setting range is 16~30ºC.
(2) During malfunction of outdoor unit or the unit is stopped because of protection, indoor unit keeps original operation status.
(3) Protection status is same as that under cooling mode.
(4) Sleep function is not available for drying mode.
(3)Heating mode
(1) Under this mode, Temperature setting range is 16~30ºC.
(2) Working condition and process for heating mode:
When turn on the unit under heating mode, indoor unit enters into cold air prevention status. When the unit is stopped or at OFF status,
and indoor unit has been started up just now, the unit enters into residual heat-blowing status.
(4)Working method for AUTO mode:
1.Working condition and process for AUTO mode:
a.Under AUTO mode, standard heating Tpreset=20ºC and standard cooling Tpreset=25ºC. The unit will switch mode automatically
according to ambient temperature.
2.Protection function
a. During cooling operation, protection function is same as that under cooling mode.
b. During heating operation, protection function is same as that under heating mode.
3. Display: Set temperature is the set value under each condition. Ambient temperature is (Tamb.-Tcompensation) for heat pump unit
and Tamb. for cooling only unit.
4. If theres I feel function, Tcompensation is 0. Others are same as above.
(5)Fan mode
Under this mode, indoor fan operates at set fan speed. Compressor, outdoor fan, 4-way valve and electric heating tube stop operation.
Indoor fan can select to operate at high, medium, low or auto fan speed. Temperature setting range is 16~30ºC.
2. Other control
(1) Buzzer
Upon energization or availably operating the unit or remote controller, the buzzer will give out a beep.
(2) Auto fan
Heating mode: During auto heating mode or normal heating ode, auto fan speed will adjust the fan speed automatically according to
ambient temperature and set temperature.
(3) Sleep
After setting sleep function for a period of time, system will adjust set temperature automatically.
(4) Timer function:
General timer and clock timer functions are compatible by equipping remote controller with different functions.
(5) Memory function
memorize compensation temperature, off-peak energization value.
Memory content: mode, up&down swing, light, set temperature, set fan speed, general timer (clock timer cant be memorized).
After power recovery, the unit will be turned on automatically according to memory content.
(6)Refrigerant recovery function:
(1) Enter refrigerant recycling function
Within 5min after energizing (unit ON or OFF status is ok), continuously press LIGHT button for 3 times within 3s to enter refrigerant
recycling mode; Fo is displayed and refrigerant recycling function is started. At this moment, the maintenance people closes liquid
valve. After 5min, stick the thimble of maintenance valve with a tool. If there is no refrigerant spraying out, close the gas valve
immediately and then turn off the unit to remove the connection pipe.
Summary of Contents for MULTI VARIABLE SERIES
Page 1: ...MULTI VARIABLE SERIES DUCT MV DxxBI SERVICE MANUAL EN ...
Page 13: ...11 Service Manual AUTO COOL DRY FAN HEAT ...
Page 14: ...12 Service Manual horizontal louvers stops at current position no display no display ...
Page 15: ...13 Service Manual Sketch map for replacing batteries ...
Page 18: ...16 Service Manual 6 3 Wired Remote Controller XK19 ...
Page 19: ...17 Service Manual ...
Page 20: ...18 Service Manual ...
Page 21: ...19 Service Manual ...
Page 22: ...20 Service Manual ...
Page 23: ...21 Service Manual memmorizing memmorizing ...
Page 24: ...22 Service Manual ...
Page 25: ...23 Service Manual ...
Page 26: ...24 Service Manual ...
Page 28: ...26 Service Manual 09 12K 18K 24K 7 1 4 7 1 5 ...
Page 29: ...27 Service Manual 7 1 6 ...
Page 30: ...28 Service Manual 7 1 7 7 1 8 ...
Page 31: ...29 Service Manual ...
Page 32: ...30 Service Manual 7 1 9 7 1 10 ...
Page 33: ...31 Service Manual 7 1 11 7 1 12 ...
Page 34: ...32 Service Manual 7 1 13 ...
Page 45: ...PARTS GUIDE MV D09BI MV D12BI MV D18BI MV D24BI DUCT MULTI VARIABLE SERIES 103 ...
Page 46: ...MV D09BI ...
Page 48: ...MV D12BI ...
Page 50: ...MV D18BI ...
Page 52: ...MV D24BI ...
Page 54: ......