Install of The Compact Panel Cassette Type Indoor Unit
6
Sponge(attachment)
Clamp(attachment)
Below 4mm
Clamp
Drain hose
Sponge (gray)
Fig.7
Drain stepup pipe note
◆
The install height of the drain raising pipe should less than 280mm.
◆
The drain raising pipe should form a right angle with the unit, and distance to unit should not beyond
300mm.
Fig.8
Instruction
◆
The slant gradient of the attached drain hose should be within 75mm so that the drain hole doesn’t has
to endure the unnecessary outside force.
Fig.9
◆
Please install the drain hose according to the following process if several drain hoses join together.
Fig.10
2 Check the smoothness of drain after installation.
◆
Check the drain state by immitting 600cc water slowly from the outlet vent or test hole.
◆
Check the drain in the state of refrigerating after installation of the electric circuit.