61
If the outer diameter of the heating pipe is 20mm and thickness is 2mm, then the minimum flow for the heating
pipe is:
It can be see that the arranged piping system for the bathroom does not meet the technical requirement and
need to combine the loops with the master room.
6.2.4 Arrangement Design of the Underfloor System for the Master and Bath Rooms
According to the calculation results, the total heat load for the master and bath rooms is 3196W, heat dissipation
per unit area is 82W/m
2
, tube spacing of the heating pipe is 300mm, and heat loss is 25.4 W/m
2
, then the total heat
loss is:
3196+1016=4212W
According to the formula Q= CρGΔT, the flow rate is
Loop quantity is 0.3622/0.18=2.012 and the round-off number is 2.
6.2.5 Check
◆
Check for the flow rate
Floor rate of each loop is within 0.25~0.5m/s and the system can run stably.
◆
Check for the tube length
When the average tube spacing is 30mm, the required length of the heating pipe per square meter is 3.5m,
length of total coils is 3.5×40=140 and length for each loop is 140/2=70.
It can be seen that the length for each loop is less than 120m and it meets the design requirement.
◆
Check for the ground average temperature
tp=tn+9.82×(qx/100) 0.969=20+9.82×(82/100) 0.969=28°C
Upper Limits and Average Floor Temperature
Average Floor Temperature
Area
Average Temperature
Maximum Temperature
Long-term Dwelling Area
24~26
28
Short-term Dwelling Area
28~30
32
Nobody Area
35~40
42
6.3 Model Selection
Heat demand for a single layer: 3196W
Heat loss for a single layer: 1016W
Total heat load for a single layer: 4212W
Total heat load of the building: 8424W
Capacity of the main unit should be larger than 8424W, so we can select: GSH-GSH-100ERB
Summary of Contents for GSH ERB-3 Series
Page 44: ...40 7 GSH 80ERB2 GSH 100ERB2...
Page 48: ...44 Parts List of GSH 120ERB GSH 140ERB GSH 160ERB 9 GSH 120ERB GSH 140ERB GSH 160ERB...
Page 53: ...49 12 GSH 120TRB2 3 GSH 140TRB2 3 GSH 160TRB2 3...
Page 108: ...104 3 3 3 2 Help Click Help and view the operation instructions of the APP...
Page 109: ...105 3 3 3 Feedback Click Feedback to submit feedback...
Page 116: ...112 3 GSH 40ERB2 GSH 60ERB2 4 GSH 80ERB2 GSH 100ERB2...
Page 131: ...127 GSH 80ERB GSH 100ERB GSH 40ERB2 GSH 60ERB2...
Page 133: ...129 GSH 120ERB 3 GSH 140ERB 3 GSH 160ERB 3 GSH 120ERB GSH 140ERB GSH 160ERB...
Page 134: ...130 4 9 Wiring of the Terminal Board GSH 40TRB GSH 60TRB GSH 80TRB GSH 100TRB...