90
3.2.4.13 Gate-Ctrl.
[Operation Instructions]
At the commissioning parameter setting page, by touching “
Gate-Ctrl.
”, the control panel will access to the
corresponding setting page.
[Notes]
●When “
Gate-Ctrl.
” has been activated; the display panel will detect the card state. When the card has inserted,
the unit will run normally. When the card is drawn out, the controller will turn off the unit at once and back to the
homepage. In this case, all touching operation become ineffective, and a prompt dialog box will pop up. The unit
will resume normal operation until the card has inserted back and the ON/OFF status of the control panel will
resume to that before the card is drawn out.
●This setting will be memorized upon power failure.
3.2.4.14 Current Limit/ Power Limit
[Operation Instructions]
1.At the commissioning parameter setting page, by touching “
C/P limit
”, it can be set to “
Off,
“
Current limit
” or
“
Power limit
”.
2.When it is set it “
Off
”, current limit and power limit both cannot be set. When it is set to “
Current limit
” or “
Power
limit
”, they can be set.
3.After that, this setting will be saved by touching the “
Save
” icon.
[Notes]
●This setting will be memorized upon power failure.
3.2.4.15 Address
[Operation Instructions]
At the commissioning parameter setting page, by touching “
Current limit
”, it can be set the address.
[Notes]
●It is used to set the address of the control panel for being integrated to the centralized control system.
●This setting will be memorized upon power failure.
●The setting range is 1~125 and 127~253.
●The defaulted address is 1 upon first power-on.
3.2.4.16 Refrigerant Recovery
[Operation Instructions]
At the commissioning parameter setting page, by touching “
Refri. recovery
”, it will access to the refrigerant
recovery page.
When “
Refri. recovery
” is set to “
On
”, the control panel will go back to the home page. At this time, any touch
operation except ON/OFF will get no response, with a prompt dialog box popping up, saying “
The refrigerant
recovery is running!
” By touching ON/OFF, refrigerant recovery will quit.
Summary of Contents for GSH ERB-3 Series
Page 44: ...40 7 GSH 80ERB2 GSH 100ERB2...
Page 48: ...44 Parts List of GSH 120ERB GSH 140ERB GSH 160ERB 9 GSH 120ERB GSH 140ERB GSH 160ERB...
Page 53: ...49 12 GSH 120TRB2 3 GSH 140TRB2 3 GSH 160TRB2 3...
Page 108: ...104 3 3 3 2 Help Click Help and view the operation instructions of the APP...
Page 109: ...105 3 3 3 Feedback Click Feedback to submit feedback...
Page 116: ...112 3 GSH 40ERB2 GSH 60ERB2 4 GSH 80ERB2 GSH 100ERB2...
Page 131: ...127 GSH 80ERB GSH 100ERB GSH 40ERB2 GSH 60ERB2...
Page 133: ...129 GSH 120ERB 3 GSH 140ERB 3 GSH 160ERB 3 GSH 120ERB GSH 140ERB GSH 160ERB...
Page 134: ...130 4 9 Wiring of the Terminal Board GSH 40TRB GSH 60TRB GSH 80TRB GSH 100TRB...