44
Outdoor unit:
Model
ASE-76AH
ASE-96AH
Power supply
380~415V-
3N-50Hz
380~415V-
3N-50Hz
Capacity of power
supply/ fuse (A)
60/40
60/40
Power supply
cable
YCW-450/750
4*6.0 mm
2
YCW-450/750
4*6.0 mm
2
Grounded wire
YCW-450/750
6.0 mm
2
YCW-450/750
6.0 mm
2
Connective wire of
indoor to outdoor
unit
RVV-300/500
4*1.0 mm
2
RVV-300/500
4*1.0 mm
2
Wire controls
connective wire
RVVP-300/300
5*0.5mm²
RVVP-300/300
5*0.5mm²
ASE-120AH
380~415V-
3N-50Hz
60/40
YCW-450/750
4*6.0 mm
2
YCW-450/750
6.0 mm
2
RVV-300/500
4*1.0 mm
2
RVVP-300/300
5*0.5mm²
6.3 Power wires
The power wires are as follows: (schematic diagram)
Indoor unit
Control wire between
indoor unit and outdoor
unit
RCCB
Manual switch
Indoor unit power supply
Outdoor unit power supply
RCCB Manual switch
220-240V~ 50Hz
380-415V 3N~ 50Hz
O
ut
do
or
un
it
Fig-35
Summary of Contents for ASE-120AH
Page 1: ...SERVICE MANUAL ASE 76AH ASE 96AH ASE 120AH CONDENSING UNITS ...
Page 2: ......
Page 11: ...8 2 Dimension Units mm 2 1 ASE 76AH ASE 96AH ...
Page 12: ...9 2 2 ASE 120AH ...
Page 18: ...15 8 1 ASE 76AH 8 Exploded View ...
Page 20: ...17 8 2 ASE 96AH ...
Page 22: ...19 8 3 ASE AH ...
Page 51: ...48 ...
Page 52: ...49 Part 4 Control 1 Central Control Monitor Optional 50 ...
Page 53: ...50 1 HQWUDO RQWURO 0RQLWRU 2SWLRQDO 0 1 2YHUYLHZ XWWRQV DQG XQFWLRQV ...
Page 54: ...51 Liquid Crystal Display ...