23
Low pressure protection
Judge 1: The wiring between the low pressure switch and main
control board is connected well or correctly
Judge 2: Whether the low pressure switch is broken
Connect it well
Validate: Short connect the low pressure switch
socket, check whether the system can run normally
Check whether the refrigerant system is ok
Yes
No
Judge 3: Check whether the outdoor ambient temperature is too low
Yes
Stop the unit
No
Judge 4: The refrigerant of the system is leakage
Yes
Validate: Connect the pressure gauge to the gauge joint of the
system, check whether the pressure is lower than 0.15MPa
Leak hunting: charge nitrogen or
refrigerant to the system, if the
leakage is serious, there will be
distinct gas leakage “cici” sound;
if the leakage is little, use the
suds(mixture of water and
abluent is also ok, if it can make
bubble) or electronic leak
detector.
Judge 5: The refrigerant pipe is blocked
Yes
Drop refrigerant, then use the high
pressure nitrogen or refrigerant to blow
pipe, vacuumize and add the refrigerant
again
No
Replace outdoor PCB
No
No
Yes
Replace low pressure switch
Summary of Contents for ASE-120AH
Page 1: ...SERVICE MANUAL ASE 76AH ASE 96AH ASE 120AH CONDENSING UNITS ...
Page 2: ......
Page 11: ...8 2 Dimension Units mm 2 1 ASE 76AH ASE 96AH ...
Page 12: ...9 2 2 ASE 120AH ...
Page 18: ...15 8 1 ASE 76AH 8 Exploded View ...
Page 20: ...17 8 2 ASE 96AH ...
Page 22: ...19 8 3 ASE AH ...
Page 51: ...48 ...
Page 52: ...49 Part 4 Control 1 Central Control Monitor Optional 50 ...
Page 53: ...50 1 HQWUDO RQWURO 0RQLWRU 2SWLRQDO 0 1 2YHUYLHZ XWWRQV DQG XQFWLRQV ...
Page 54: ...51 Liquid Crystal Display ...