background image

 

Symptoms Causes 

Solution 

Unit does not start 

•   

Power failure.  

•   

Power switch is off.  

•   

Fuse of power switch may have burned.  

•   

Batteries of remote controller exhausted 

or other problem of controller.

 

•   

W ait for the comeback of power.  

•   

Switch on the power.  

•   

Replace the fuse.  

•   

Replace the batteries or check the 

controller.

 

Air flowing normally but 
completely can't cooling 

•   

Temperature is not set correctly.  

•   

Be in 3 minutes protection of compressor.

 

•   

Set the temperature properly.  

•   

Wait.

 

Units start or stop 
frequently 

•   

Refrigerant is too little or too much.  

•   

Airor no concreting gas in the refrigerating 

circuit.  

•   

Compressor is malfunction.  

•   

Voltage is too high or too low. 

•   

System circuit is blocked.

 

•   

Check leakage, and rightly recharge 

refrigerant.  

•   

Vacuum and recharge refrigerant.  

•   

Maintenance or change compressor. 

 

•   

Install manostat.

 

Low cooling effect 

•   

Outdoor unit and indoor unit heat 

exchanger is dirty.  

•   

The air filter is dirty.  

•   

Inlet/outlet of indoor/outdoor units is 

blocked.  

•   

Doors and windows are open  

•   

Sunlight directly shine.  

•   

Too much heat resource.  

•   

Outdoor temp. is too high.  

•   

Leakage of refrigerant or lack of 

refrigerant.

 

•   

Find reasons and solution.  

•   

Clean the heat exchanger.  

•   

Clean the air filter.  

•   

Eliminate all dirties and make air 

smooth.  

•   

Close doors and windows.  

•   

Make curtains in order to shelter from 

sunshine.  

•   

Reduce heat source.  

•   

AC cooling capacity reduces (normal).

 

Low heating effect 

•   

Outdoor temperature is lower than 7°C .  

•   

Doors and windows not completely 

closed.  

•   

Leakage of refrigerant or lack of 

refrigerant.

 

•   

Check leakage and rightly recharge 

refrigerant.  

•   

Use heating device.  

•   

Close doors and windows.  

•   

Check leakage and rightly recharge 

refrigerant.

 

Table 8-2 

 

Symptoms Causes 

Solution 

The fan speed can not be 
changed. 

• 

Check whether the MODE indicated on the 

display is "AUTO"

 

When the automatic mode is selected, the 
air conditioner will automatically change 
the fan speed. 

• 

Check whether the MODE indicated on the 

display is "DRY"

 

When dry operation is selected, the air 
conditioner automatically change the fan 
speed. The fan speed can be selected 
during "COOL" , "FAN ONLY", and 
"HEAT". 

The remote controller 
signal is not transmitted 
even when the ON/OFF 
button is pushed. 

• 

Check whether the batteries in the remote 

controller are exhausted.

 

The power supply is off. 

The TEMP. indicator does 
not come on. 

• 

Check whether the MODE indicated on the 

display is FAN ONLY

 

The temperature cannot be set during FAN 
mode. 

The indication on the 
display disappears after 
a lapse of time. 

• 

Check whether the timer operation has 

come to an end when the TIMER OFF is 
indicated on the display.

 

The air conditioner operation will stop up 
to the set time. 

The TIMER ON indicator 
goes off after a lapse of 
certain time. 

• 

Check whether the timer operation is 

started when the TIMER ON is indicated on 
the display.

 

Up to the set time, the air conditioner will 
automatically start and the appropriate 
indicator will go off. 

No receiving tone sounds 
from the indoor unit even 
when the ON/OFF button 
is pressed. 

• 

Check whether the signal transmitter of the 

remote controller is properly directed to the 
infrared signal receiver of the indoor unit 
when the ON/OFF button is pressed.

 

Directly transmit the signal transmitter of 
the remote controller to the infrared signal 
receiver of the indoor unit, and then 
repeatly push the ON/OFF button twice. 

Table 8-3 

 

Summary of Contents for ASC-60AN

Page 1: ...USER S MANUAL ASC 60AN UNI ON OFF SERIES ...

Page 2: ... Original instruction ...

Page 3: ...splay panel Drain pipe Remote controller Air outlet Refrigerant pipe Air filter inside air in grill Air inlet Air inlet Air outlet NOTE All the pictures in this manual are for explanation purpose only They may be slightly different from the air conditioner you purchased depend on model The actual shape shall prevail ...

Page 4: ... perform this work Do not dispose this product as unsorted municipal waste Collection of such waste separately for special treatment is necessary Do not dispose of electrical appliances as unsorted municipal waste use separate collection facilities Contact you local government for information regarding the connection systems available If electrical appliances are disposed of in landfills or dumps ...

Page 5: ... including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do not play with the appliance If the supply cord is damaged it must be replaced by the manufacturer its service ...

Page 6: ...emain open air will flow out of your room causing a decrease in the cooling or heating effect Never place objects near the air inlet or the air outlet of the unit It may cause deterioration in the effect or stop the operation Set the timer If you don t plan to use the unit for a long time please take the batteries from the remote controller When the power is on some energy will be consumed even if...

Page 7: ... and connect the control box cables to the corresponding terminators of the main body Fig 6 1 Fig 6 2 Fig 6 3 Fig 6 4 7 FOLLOWING SYMPTOMS ARE NOT AIR CONDITIONER TROUBLES Symptom 1 The system does not operate The air conditioner does not start immediately after the ON OFF button on the romote controller is pressed If the operation lamp lights the system is in normal condition To prevent overloadi...

Page 8: ...ur stop operation shut off the power and contact with your dealer The operation lamp is flashing rapidly 5Hz This lamp is still flashing rapidly after turn off the power and turn on again See in Table 8 1 Remote controller receives malfunction or the button does not work well A safety device such as a fuse a breaker frequently actuates Obstacles and water enter the unit Water leaks from indoor uni...

Page 9: ... device Close doors and windows Check leakage and rightly recharge refrigerant Table 8 2 Symptoms Causes Solution The fan speed can not be changed Check whether the MODE indicated on the display is AUTO When the automatic mode is selected the air conditioner will automatically change the fan speed Check whether the MODE indicated on the display is DRY When dry operation is selected the air conditi...

Page 10: ...3X2 housed in the rear part and protected by a cover 1 Remove the cover by pressing and sliding off 2 Remove the old batteries and insert the new batteries placing the and ends correctly 3 Reattach the cover by sliding it back into position NOTE When the batteries are removed the remote controller erases all programming After inserting new batteries the remote controller must be reprogrammed CAUTI...

Page 11: ... LCD shows F2 Press the TEMP UP to control the faceplate up and press the TEMP DOWN to control the faceplate down Press any button to exit the faceplate setting state then the LCD back to the normal display TIMER ON Button Press this button to activate the Auto on time setting Each press will increase the time setting in 30 minutes increments up to 10 hours then at 1 hour increments up to 24 hours...

Page 12: ... MODE display FAN mode FAN SPEED display Displays the selected fan speed AUTO HIGH MED if applicable and LOW Nothing displays when the fan speed is selected in AUTO speed When AUTO or DRY Mode is selected there will be no signals displayed TIMER display This display area shows the settings of the TIMER That is if only the Auto on time function is set it will display TIMER ON If only the Auto off t...

Page 13: ...available 1 Press the MODE button to select COOL HEAT cooling heating models only or FAN mode 2 Press the TEMP button to set the desired temperature The temperature can be set within a range of 17 O C 30 O C in 1 O C increments 3 Press the FAN SPEED button to select the fan speed in four steps Auto Low Med or High 4 Press the ON OFF button to start the air conditioner NOTE In the FAN mode the sett...

Page 14: ...o 24 hours 3 After setting the TIMER ON there will be a one half second delay before the remote controller transmits the signal to the air conditioner Then after approximately another 2 seconds the signal h will disappear and the set temperature will re appear on the LCD display window To set the Auto off time 1 Press the TIMER OFF button The remote controller shows TIMER OFF the last Auto off set...

Page 15: ...t to stop the air conditioner after you go to bed and start it again in the morning when you wake up or when you return home Example To stop the air conditioner 2 hours after setting and start it again 10 hours after setting 1 Press the TIMER OFF button 2 Press the TIMER OFF button again to display 2 0h on the TIMER OFF display 3 Press the TIMER ON button 4 Press the TIMER ON button again to displ...

Page 16: ...ELECTRIC SCHEMATIC DIAGRAM ASC 60AN indoor unit ASC 60AN outdoor unit ...

Page 17: ... 5MPa SUCTION INDOOR MODEL ASC 60AN COOLING CAPACITY 14 9kW HEATING CAPACITY 17 0kW 111 1kg R410A 3500g 7000W 19 0A 1 5MPa 4 2MPa SPLIT UNIVERSAL AIR CONDITIONER OUTDOOR UNIT OUTDOOR MODEL 380 415V 3N 50Hz IP 24 REFRIGERANT EXCESSIVE OPERATING PRESSURE WEIGHT OUTDOOR POWER SOURCE OUTDOOR UNIT RESISTANCE CLASS DISCHARGE ASC 60AN SUCTION RATED INPUT RATED CURRENT RATING LABEL ...

Page 18: ... A higher G lower kW Air Conditioner 3015 14 95 2 48 E 55 17 A B C D E F G ASC 60AN ASC 60AN Manufacturer Outside Unit Inside Unit Energy A B C D E F G More efficient Less efficient Noise dB A re 1 pW Further information is contained in product brochures Norm EN 14511 Air conditioner Energy Label Directive 2002 31 EC Annual energy consumption kWh in cooling mode kW Actual consumption will depend o...

Page 19: ......

Page 20: ...s located INFORMATION CONCERNING USED REFRIGERANT MEDIUM This unit is containing fluorinated gases included in the Kyoto protocol The maintanance and the liquidation must be carried out by qualified personel Type of refrigerant R410A The composition of the cooling medium R410A 50 HFC 32 50 HFC 125 The quantity of the refrigerant please see the unit label The value GWP 2088 GWP Global Warming Poten...

Reviews: