REV11119
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | [email protected] |
SimpliPhiPower.com
| 14 |
3.6
– Knock Out Locations
Three 1.375-inch OD knockouts and one 2-inch OD knockout are located on both sides of the AccESS
cabinet. They can be used for AC or DC inputs. Not all knockouts must be used.
Figure 5.0
– AccESS Cabinet Knock-Outs (sides)
3.7
– Pad Mounting
3.7.1
– Pad Requirements
The AccESS must be installed and secured on level concrete. For a pre-cast concrete pad, a
4”
minimum thickness is required.
The pad should be 3” wider than the AccESS on all sides (34” x
22” x 4”).
The AccESS is not suited for wall mounting. Any attempt to wall mount the AccESS unit will void
the Warranty.
3.7.2
– Pad Mounting the SimpliPhi AccESS
Six 1-inch knockouts are located in the base of the AccESS for tool accessibility when mounting
the AccESS to the concrete pad. Cover knockout holes with sealing tape after pad mount
installation, and prior to installing the PHI 3.8 Batteries into the base of the cabinet. Any attempt
to wall mount the AccESS unit will void the Warranty.
Secure the AccESS to the concrete with concrete anchors, such as threaded rods, masonry bolts,
or carriage bolts, minimum ½” diameter. See Figure 6.0 below for details.