background image

TrueSTART II

 Installation & Service

Instrument

To Test
IDNet/IDNAC
X-Talk

IDC
NAC

Green wire must be connected to earth when
conducting an earth fault test or search.

WARNING:Test the wire with voltimeter and
verify no external voltage source is present
before connecting this instrument. 

Use up/down arrow and keys to move
between menu choices

To Navigate Menus

Press ENT ket to select a menu choice

Press MENU key to back out of a menu
choice

Connect

Red +, Black -

Red to CHNL1+

Green to CHNL2+

Red+, Black -

Red to Alarm-

Black to Alarm+

ON

OFF

ENT

MENU

F1

F2

Main Menu

Press ENT to select

[Earth Fault Test]

R

579-1030 Rev A

Summary of Contents for TrueSTART II

Page 1: ...verify no external voltage source is present before connecting this instrument Use up down arrow and keys to move between menu choices To Navigate Menus Press ENT ket to select a menu choice Press ME...

Page 2: ...t Shorts 9 IDNAC 10 Power Option 11 X Talk Test 12 Test IDC zone 13 Test NAC Signal 14 Saving IDNet and IDNAC Test Results 15 Recalling Test Results 15 Upload to PC 15 System Settings 16 Backlight Tim...

Page 3: ...devices are correctly installed before connecting the wires to the FACP Power Sources The TSIT operates from multiple power sources Lithium Ion Battery AC Adapter Any 24V DC source using the Auxiliary...

Page 4: ...xtend the reach of the AC adapter Provide power via alligator clips to ZAMs and other 24V powered devices when used with the AC adapter Power the tester from an FACP The output from the AC adapter wil...

Page 5: ...C addressable devices Simplex NACs and Simplex IDCs Connect and test only these types of circuits Before connecting the tester to any circuit for testing verify that the circuit is not connected to an...

Page 6: ...und such as building steel To detect every earth fault you must test the positive lead and the negative lead of a circuit independently If there are earth faults on both positive and negative leads it...

Page 7: ...one repeating the process To test an IDNet channel with IDNet Isolators or TrueAlarm Isolator Bases Earth Fault Search must also be run on the IDNet channel IDNet The user should have a list of IDNet...

Page 8: ...ompare it to the devices that are supposed to be installed Press ENT to review the results of the scan Use the up down arrows to scroll through the menu choices The choices are to review Totals review...

Page 9: ...in repeating the steps outlined earlier in this document If you just wish to run the Duplicate Address test scroll through the menu choices until that selection is displayed and press ENT The IDNet Te...

Page 10: ...rom the TSIT The TSIT will not power the appliances into alarm mode At the completion of the scan review the summary of devices detected and compare to the list of devices that are supposed to be inst...

Page 11: ...evice It is useful to also take note of any missing devices before going out to correct duplicates IDNAC Tests In the example above two devices were set to address 003 and let s assume a device was mi...

Page 12: ...may be conducted on two IDNet channels connect IDNet as described in the table It may also be used between RUI and IDNet or IDNet and IDNAC To Test Connect IDNet RED lead to IDNet wiring of Channel A...

Page 13: ...d by the electromagnetic field of a signal interfering with the electrical signal on an adjacent conductor Inductive coupling interference is worse when a current changes rapidly in amplitude Signals...

Page 14: ...ng Test NAC Signal Test conventional Notification Appliance Circuits with this menu selection At the top level menu navigate to Test NAC signal with the up down arrow keys and press ENT to select the...

Page 15: ...will surround the slot number and the or keys are used to select the desired slot number 1 60 Press ENT to save to this new slot Note that the TSIT allows you to override a previously filled memory sl...

Page 16: ...t be erased System Settings The System Settings menu option includes menu choices that allow you to view information clear memory slots and set TSIT options System Settings Backlight Timer Battery Sel...

Page 17: ...or keys to select the slot to erase or select Clear All to erase all memory slots The ENT key must be pressed twice to erase the memory The second key press is a confirmation of the requested operatio...

Page 18: ...dard base SPHOTO TrueAlarm photoelectric sensor sounder base RPHOTO TrueAlarm photoelectric sensor relay base IPHOTO TrueAlarm photoelectric sensor isolator base QPHOTO TrueAlarm quick connect photoel...

Page 19: ...ted CO SOUNDER BASE TrueAlarm CO sensor base with sounder no head inserted UNKNOWN DEVICE Unrecognized device type Type Description INVALID ADDRESS A device was found at one of the following addresses...

Page 20: ...sual appliance A V Audio Visual appliance ISO Isolator Type Description DUPLICATE 2 or more device set to the same address NO ANSWER A device that previously communicated no longer does OPEN Other por...

Page 21: ...0 Candela 75Cd 75 Candela 75WP Cd 75 Weatherproof Candela 110Cd 110 Candela 135Cd 135 Candela 185Cd 185 Candela FACP Cd Candela configured by FACP Lens Color Clear Clear lens cover Color Colored lens...

Page 22: ...nstaller will automatically start If it does not automatically start use Windows Explorer to open the CD folder and double click on the file setup exe You must accept the license agreement to install...

Page 23: ...ordered from stock SKU Description TSI 24V TSI TSIT 24 V wall wart TSI BATTERY TSI TSIT 24 V battery TSI CHARGER TSI TSIT battery charger TSI PROTECT TSI TSIT case protector TSI TLEADS TSI TSIT test...

Page 24: ...specifications and other information shown were current as of document revision date and are subject to change without notice TYCO SIMPLEX and the product names listed in this material are marks and o...

Reviews: