background image

 

IDNAC SLC Operation Advantage 

 

TrueAlert V/O Appliances with Addressable 
Strobes on IDNAC SLCs

 provide visible notification 

using a single two-wire circuit that also 

confirms 

connection to the individual notification appliance’s 
electronic circuit

. This operation increases circuit 

supervision integrity by providing supervision that 
extends beyond the appliance wiring connections.

 

Reduced current allows efficient IDNAC SLC 
operation.

 With 

IDNAC SLCs

, a 

constant

 29 VRMS 

source voltage is maintained, even during battery standby, 
allowing strobes to operate at higher voltage with lower 
current and ensuring a consistent current draw and voltage 
drop margin under both primary power and secondary 
battery standby. Efficiencies include wiring distances up to 
2 to 3 times farther than with conventional notification, or 
support for more appliances per IDNAC SLC, or use of 
smaller gauge wiring, or combinations of these benefits, all 
providing installation and maintenance savings with high 
assurance that appliances that operate during normal system 
testing will operate during worst case alarm conditions. 

Reducing Installation and Testing Time.

 With 

separate controls on the same two-wire SLC, installation 
time and expense for both retrofit and new construction 
can be significantly reduced. When Class B wiring is 
used, 

wiring can be “T” tapped

, allowing more savings in 

distance, wire, conduit (size and utilization), and overall 
installation efficiency. Use of the magnet test feature 
improves installation efficiency. TrueAlert device reports 
conveniently identify information about each connected 
appliance. 

By providing an amber lens strobe with a clear lens 
strobe, the combination strobe assembly allows a single 
electrical installation to provide both types of visible 
notification. 

 

 

TrueAlert Addressable Diagnostics 

 

Test Features.

 Controllers can be selected to pulse each 

appliance’s LED when it receives a supervision poll. When 
the controller is selected for diagnostic mode, the appliance 
magnet test feature provides a response at the individual 
appliance being tested.  

Silent Appliance Magnet Test.

 In this test mode, in 

response to the magnet test, the appliance LED pulses 
sequentially to conveniently indicate the appliance’s 
address.  

Operational Appliance Testing.

 In this test mode, after 

the address is indicated by pulsing the appliance LED, the 
strobe will briefly flash to indicate proper operation. 

TrueStart Instrument Two (TSIT).

 The 2nd generation 

of the Simplex TrueStart Test Instrument adds testing of 
IDNAC SLC wiring and TrueAlert (and TrueAlert ES) 
appliances to its ability to test IDCs, NACs, and IDNet 
communications 

before

 

connection to the control panel

Please contact your local Simplex representative for 
additional information. 

TrueAlert Addressable Wiring Isolator  

 

Isolator Model

 

4905-9929 

is available for remote 

mounting on TrueAlert addressable circuits to isolate short 
circuited wiring from functioning wiring. (Refer to data 
sheet S4905-0001 for additional information.)

 

TrueAlert Device Reports 

detail type, candela rating, 

and location per appliance (see sample below, amber lens 
type is AMB).  

 

S4906-0009-3  3/2014

Model 

Housing 

Color 

Description 

Dimensions 

4906-9208 Red Multi-Candela Addressable Combination Strobe assembly with 

amber lens, ALERT strobe on top and clear lens, FIRE strobe 
on bottom; intensity selectable as: 15, 30, 75, or 110 candela 

10 ¾” H x 5 

” W x 3 

15

16

” D 

(273 mm x 130 mm x 100 mm) 

4906-9211 White 

4905-9837 Red 

Surface Mount Adapter Skirt, use to cover surface mounted 
electrical boxes 

10 ½” H x 5 ¼” W x 1 ¾” D 
(267 mm x 133 mm x 44 mm) 
Total depth with strobe assembly 
= 5 

” (143 mm) 

4905-9847 White 

4905-9840 Red 

Adapter Plate for mounting to installed Simplex Model 
2975-9145 box;

 for flush mounted boxes only

 

12 

5

16 

” H x 5 ¾” W x 0.06 thick 

(313 mm x 146 mm x 1.5 mm) 

Service Port 

Page 1

REPORT 5 : TrueAlert Device Report 

12:34:56am  MON  17-Mar-14

 
POINT ID 

 
CUSTOM LABEL 

DEVICE

TYPE

 

CANDELA 

T14-1-1 

Location Label . . . up to 40 characters

V/O

15 

T14-1-2 

Break Room 5 

A/V

110 

T14-1-3 

Boiler Room Fire 

A/V

75 

T14-1-4 

Boiler Room Alert 

AMB

75 