3
S4906-0009-3 3/2014
Strobe Details
2
1
3
4
Wiring
access hole
Wiring
terminals
Transparent
housing and lens
assembly (clear
for FIRE, amber
for ALERT)
Address setting
DIP switch
Hole for bracket
mounting
Strobe intensity viewing slot
Intensity selection plug, accessible
only from rear of housing; factory
setting is FACP, controlled by panel
110
75
30
15
FACP
LED indicator
Hole for bracket mounting
4" square box outline, flush
mount or surface mount
IMPORTANT!
WALL MOUNT INSTALLATION HEIGHT REFERENCE
80" (2.03 m)
minimum for
4" square box
and 3-gang surface
mount box
81" (2.06 m)
minimum for
4-gang flush
mount box
4-gang box outline,
flush mount
3-gang box outline,
surface mount
Clear/Amber
Strobe assembly
5" (127 mm)
Bottom of FIRE lens is either
even with, or slightly above
bottom of 4" square boxes and
3-gang surface mount box
NFPA 72 requires that the
entire FIRE lens be not less
than 80" and not greater
than 96" above the finished
floor
Adapter skirt (shown
for reference)
Clear lens strobe
(supplied)
Amber lens
strobe (supplied)
Mounting bracket
(supplied)
Housing cover
(supplied)
4" (102 mm) square box for
flush mount or surface mount,
1-1/2" (38 mm) deep, by others
Alternate surface mount electrical boxes, 3-gang mounted
vertically; Steel City 3G-1/2 (or 3/4), or Raco 952; 8-5/8" x 4-1/
2" x 1-5/8" deep (219 mm x 114 mm x 41 mm), by others
Screw (1) to attach
cover, and screws
(4) to attach strobes
to bracket (supplied)
Optional Adapter Skirt for
surface mounted boxes
(ordered separately)
Alternate flush mount electrical box, 4-gang
mounted vertically; Steel City 4G4D 1/2; 7-5/8" x 4"
x 2-1/8" D; (194 mm x 102 mm x 54 mm), by others
Magnetic test locations
Strobe Details and Mounting Height Reference
Installation Reference