background image

 

 

S4906-0009-3  3/2014

Strobe Details

2

1

3

4

Wiring

access hole

Wiring

terminals

Transparent

housing and lens

assembly (clear

for FIRE, amber

for ALERT)

Address setting

DIP switch

Hole for bracket

mounting

Strobe intensity viewing slot

Intensity selection plug, accessible

only from rear of housing; factory

setting is FACP, controlled by panel

110
75
30
15

FACP

LED indicator

Hole for bracket mounting

 

 

4" square box outline, flush 
mount or surface mount

IMPORTANT! 

WALL MOUNT INSTALLATION HEIGHT REFERENCE

80" (2.03 m) 
minimum for 

4" square box 

and 3-gang surface 

mount box

81" (2.06 m)
minimum for 
4-gang flush 

mount box

4-gang box outline, 
flush mount

3-gang box outline, 
surface mount

Clear/Amber 

Strobe assembly

5" (127 mm) 

Bottom of FIRE lens is either 

even with, or slightly above 

bottom of 4" square boxes and 

3-gang surface mount box

NFPA 72 requires that the 

entire FIRE lens be not less 

than 80" and not greater 

than 96" above the finished 

floor

Adapter skirt (shown 

for reference)

 

 

Clear lens strobe 
(supplied)

Amber lens 

strobe (supplied)

Mounting bracket 
(supplied)

Housing cover 

(supplied)

4" (102 mm) square box for 
flush mount or surface mount, 
1-1/2" (38 mm) deep, by others

Alternate surface mount electrical boxes, 3-gang mounted 

vertically; Steel City 3G-1/2 (or 3/4), or Raco 952; 8-5/8" x 4-1/

2" x 1-5/8" deep (219 mm x 114 mm x 41 mm), by others

Screw (1) to attach 

cover, and screws 

(4) to attach strobes 

to bracket (supplied)

Optional Adapter Skirt for 

surface mounted boxes 

(ordered separately)

Alternate flush mount electrical box, 4-gang 

mounted vertically; Steel City 4G4D 1/2; 7-5/8" x 4" 

x 2-1/8" D; (194 mm x 102 mm x 54 mm), by others

Magnetic test locations

 

 

 Strobe Details and Mounting Height Reference 

 Installation Reference 