8 June 2018 • Simplex Service 800
-637-
8603 • Page
11 of 19
Swift-E / Swift-E+ Load Bank Manual
IV-D. Current Transformer Ratio
The first setting you can change is the Current Transformer Ratio. To do so, press the (up)
and (down) buttons until the desired number is displayed, then press the (menu) button.
Note: The ratio is set at the factory (100:5 for the Swift-E and 150:5 for the Swift-E+) and
should not need to be changed.
IV-E. Meter Display
After the Current Transformer Ratio is set, you can change the default
display for the bottom display on the meter. There are four options:
Loop, which will cycle through three following measurements:
1.
FrQ, which will show the power frequency.
2.
ACt, which will display the load generated, measured in kilowatts.
3.
COS, which will show the power factor.
Make your selection by pressing the up and down buttons to cycle through the options. Press
the MENU button again to set the display. This selection is stored in non-volatile memory
and will remain set even after the unit is unplugged.
When the unit is operating, pressing the menu button will cycle the display through the
three measurements.
Volts, Amps, and Hertz
0.5% + 1 digit
Kilowatts
1.0% + 2 digits
Power Factor
0.5% + 2 digits
Figure 3: Meter
Table 3: Meter Accuracy