3-11
Note:
Prior to selecting the pulse format rate, ask an authorized person at the
central station whether the required pulse rate is 20 pulses per second
(default) or 10 pulses per second.
26. Press [
↵
] or [
↓
]. Screen displays:
Scroll to the desired pulse format rate.
27. Press [
↵
] or [
↓
]. Screen displays:
Leave as is (function not included in CCDACT).
28. Press [
↵
] or [
↓
]. Screen displays:
Scroll to select YES or NO.
Note:
YES (15 second delay) is sometimes used in residential applications to
delay reporting of alarms. Use NO for all other applications.
29. Press [
↵
] or [
↓
]. Screen displays:
Scroll to select the desired choice (TONE ELSE PULSE is default).
Note:
Prior to selecting dial mode, ask an authorized person at the central
station whether the required dial mode is tone, pulse, or tone else
pulse (default).
30. Press [
↵
] or [
↓
]. Screen displays:
Scroll to select the desired choice.
Note:
Prior to selecting pulse frequencies, ask an authorized person at the
central station whether the required pulse frequencies are 1900
DATA/1400 ACK (default) or 1800 DATA/2300 ACK.
Continued on next page
Programming the CCDACT,
Continued
Programming (Continued)
26>PULSE FORMAT RATE
[20]
27>ANSWER RING COUNT
[00] - DISABLED
28>DIAL DELAY
[NO]
30>PULSE FREQUENCIES
[1900 DATA/1400 ACK]
29>DIAL MODE
[TONE ELSE PULSE]
firealarmresources.com
Summary of Contents for Contact Closure DACT
Page 2: ...1 2 firealarmresources com ...
Page 4: ...ii firealarmresources com ...
Page 10: ...viii firealarmresources com ...
Page 16: ...1 6 firealarmresources com ...
Page 54: ...3 1 firealarmresources com ...
Page 58: ...3 1 firealarmresources com ...
Page 59: ...3 2 firealarmresources com ...