4100ES-S1 Programming Guide
Document: LT0400
Addressable Device Settings
6-4
6.3.3
4090-9002 Relay IAM
Device Type
RIAM
– Standard Setting
Point Type
RELAY
– General Purpose relay.
TRELAY
– Fault Relay on until fault cleared
6.3.4
4090-9007 Signal ZAM
Device Type
SIGIAM
– Signal IAM - IDNet
Point Type
RELAY
– General Purpose Supervised relay (under Custom Control).
SIGNAL
– Alarm Relay on until Alarm is cleared
6.3.5
4090-9101 Monitor ZAM
Device Type
MBZAM
– Standard Setting
Point Type
FIRE
– Standard setting
6.3.6
4190-9050 4-20mA Analog Monitor ZAM
Device Type
ANAMON
– Standard Setting
Point Type
The Point Types are custom configurable using the
AMON Pt Type
Tab. The Point
types need to be configured before the 4190-9050 is added.
6.3.7
4090-9118 Relay IAM with T-Sense Input
This device has multiple sub points. The sub points can have the point type changed depending on
the operation.
Mx-x-0 Parent Point
Device Type
TRIAM
– Standard setting
Point Type
UTILITY
– Standard setting
Mx-x-1 1
st
Sub Point (relay output)
Device Type
MRELAY
– Fixed Device type
Point Type
RELAY
– General Purpose relay
TRELAY
– Fault Relay on until fault cleared
Summary of Contents for 4100ES-S1
Page 1: ...4100ES S1 Fire Indicator Panel Programming Guide Australian Programming Guide LT0400 Issue 1 5...
Page 2: ......
Page 7: ...Document LT0400 4100ES S1 Programming Guide Introduction 1 1 1 Introduction...
Page 10: ...4100ES S1 Programming Guide Document LT0400 Introduction 1 4 THIS PAGE IS INTENTIONALLY BLANK...
Page 11: ...Document LT0400 4100ES S1 Programming Guide System Overview 2 1 2 System Overview...
Page 39: ...Document LT0400 4100ES S1 Programming Guide Adding Zone Displays 7 1 7 Adding Zone Displays...
Page 61: ...Document LT0400 4100ES S1 Programming Guide Custom Control 9 1 9 Custom Control...
Page 69: ...Document LT0400 4100ES S1 Programming Guide AS1668 Fan Controls 10 1 10 AS1668 Fan Controls...
Page 95: ...Document LT0400 4100ES S1 Programming Guide Appendices 12 1 12 Appendices...