In a large zone with multiple amplifiers across
several card cages, how can I get tone and
message synchronisation?
Use one amplifier in the zone as a "master" and configure all the
amplifiers for the same zone in other card racks as "slaves" - use an
ALIM modified per fig 3 of LT0372 to monitor the "master" amplifier's
100V line and feed it to the local audio input of the "slaves". "Slaves"
supervise their speaker line, but don't ever select anything but the local
input.
LT0372 (also PBQ0072 for
general ideas like this)
Installation
Simplex® T3 Strobes not functioning
Simplex® T3 strobes only work on EVAC.
1) The Positive should be wired to Terminal B and the Negative should
be wired to Terminal A.
2) Dip switch setting (5, 6, 7, 8) have to be (OFF, ON, ON, ON)
PBQ0095
Servicing
Comms light (yellow) is not flashing. One LED
(green) is flashing; 8-10V between comms. Panel
displays zones 3, 4 & 5 in Audio Fault.
The panel has Faulty Strobe Card. After swapping two strobe cards
over, the fault cleared from the panel and followed the faulty strobe card
(when tested in another panel).
Servicing
An Audio line fault is observed on Zones 2 & 3
After replacing the amps and transformers the fault still did not clear.
The ribbon cable may be at fault or damaged. The red ribbon should
point to pin number 1.
Summary of Contents for 4100 Classic
Page 1: ...DIS FNG Simplex Fire Products Fault Assistance Guide...
Page 4: ...1 0 Identifying Simplex 4100 Series Faults...
Page 26: ...Page 25 of 60 2 0 4100 Crash Codes General Information...
Page 35: ...Page 34 of 60 34 of 60 of 60 of 5 of 1 60 4 0 Identifying F3200 Faults...
Page 42: ...Page 41 of 60 41 of 60 of 60 of 5 of 1 60 5 0 Identifying faults on a QE90...
Page 44: ...Page 43 of 60 43 of 60 of 60 of 5 of 1 60 5 2 ECP versions 2 xx 4 xx 6 xx System Fault Display...
Page 55: ...Page 55 of 60 5 10 ECM Networked System System Fault Display...