1.1.2.3.1 Class ‘A’ Abnormal
Description:
The addressable loop or RUI Bus has an open circuit.
Possible causes:
Open circuit in the wiring loop
Bad connection at addressable point (on addressable loop faults).
Bad connection at remote transponder or LCD Annunciator (for RUI Bus faults)
Faulty addressable loop or RUI card
-
Check this fault by „looping out‟ the A and B terminals on the RUI/Mapnet/IDNet card to clear
the fault. If fault does not clear then card may be faulty
1.1.2.3.2 Channel Failure Abnormal
Description:
The Loop card cannot communicate with any device on the loop. Be aware all devices associated with this
loop will indicate a „Normal‟ state to prevent multiple faults per display.
Possible causes:
The Loop has a Short circuit
The Loop has an Earth fault
The Loop is not connected or incorrectly connected
1.1.2.3.3 Channel Initialization Abnormal
Description:
This fault typically occurs at startup with IDNet loops and will normally clear after a couple of minutes if a lot
of Isolators are fitted.
Possible causes:
If the fault continually re-appears the loop length maybe too long or too noisy – Contact your local
Simplex® branch for assistance
Possible bad device causing communication errors
-
Disconnect devices at half way points until the fault clears to locate the faulty device
Summary of Contents for 4100 Classic
Page 1: ...DIS FNG Simplex Fire Products Fault Assistance Guide...
Page 4: ...1 0 Identifying Simplex 4100 Series Faults...
Page 26: ...Page 25 of 60 2 0 4100 Crash Codes General Information...
Page 35: ...Page 34 of 60 34 of 60 of 60 of 5 of 1 60 4 0 Identifying F3200 Faults...
Page 42: ...Page 41 of 60 41 of 60 of 60 of 5 of 1 60 5 0 Identifying faults on a QE90...
Page 44: ...Page 43 of 60 43 of 60 of 60 of 5 of 1 60 5 2 ECP versions 2 xx 4 xx 6 xx System Fault Display...
Page 55: ...Page 55 of 60 5 10 ECM Networked System System Fault Display...