1.1.5 4100-0157A Battery Charger Faults
There are a number of Battery Charger Faults that can arise during the operational lifetime of a panel. You may
observe one of the following Faults;
Charger 2% out of range
Battery Charger Supply incorrect
The most common cause is one or possibly both batteries are faulty. Before proceeding to adjust the power
supply as described below, measure the voltage of each battery while it is under load. Both batteries should
measure within 0.1v of the other
To correctly measure the output voltage you will need to follow the steps below.
1. To prevent damage to the system, disconnect the batteries & power down the system, disconnect
the power & comms harnesses from the Power Supply.
2. Connect the Multimeter to the battery leads (with batteries disconnected), power up & measure
the voltage. Calculate the difference between the measured voltage & 27.6v.
NOTE
: After 90 seconds, the voltage will drop to <24v. If this happens, power down & start
again
.
3. Connect the Multimeter to the A or B tap on TB2. Measure the voltage. Adjust the trim-pot (refer
to the Trimpot Location diagram found on Page 22) so the voltage increases (or decreases) by
the difference calculated in step 1.
Summary of Contents for 4100 Classic
Page 1: ...DIS FNG Simplex Fire Products Fault Assistance Guide...
Page 4: ...1 0 Identifying Simplex 4100 Series Faults...
Page 26: ...Page 25 of 60 2 0 4100 Crash Codes General Information...
Page 35: ...Page 34 of 60 34 of 60 of 60 of 5 of 1 60 4 0 Identifying F3200 Faults...
Page 42: ...Page 41 of 60 41 of 60 of 60 of 5 of 1 60 5 0 Identifying faults on a QE90...
Page 44: ...Page 43 of 60 43 of 60 of 60 of 5 of 1 60 5 2 ECP versions 2 xx 4 xx 6 xx System Fault Display...
Page 55: ...Page 55 of 60 5 10 ECM Networked System System Fault Display...