9-26
4007ES Panel Programmer Manual (
579-1167)
Custom Control,
Continued
Suppression
Release Use
Cases
Initial data window
• Program#: 3
Note:
It is always 3 on a 4007ES.
• Check
Enhanced Power Supply
because we have an IDNAC channel.
• Uncheck
Cross Zone (Dual Detector)
.
Note:
Without cross zone the audible notification automatically defaults to Fast March Time
(March120).
Abort Logic Window
• Set
Immediate Release (No Delay)
.
Timer Configurations
• Uncheck
Manual Release
to set it a 0.
• Uncheck
Detector Release Delay
to set it at 0.
Hazard Area Lists window
• Press
Manual Release Points
and select the manual release point at M1-11-0.
• Press
Automatic Release Points
and select Automatic Release Points at M1-18-0.
• Do not add any devices to
Abort Switches
.
• Do not add any devices to
Release Warning Points
.
• Press
Suppression Dump Points
and select SIG3 and M1-36-0.
• Press
Release Notification Audible NACs
and select SIG913.
• Press
Release Notification Visible NACs
and select SIG915.
Table 9-6 describes actions and their corresponding responses.
Table 9-6. Immediate Release, Actions and Responses
Action
Response
First detector is
triggered
RELSIG turns on steady. RELVIS turns on. SUPRELS NAC turns on steady and
SRP output turns on steady.
Summary of Contents for 4007ES Panels
Page 1: ...4007ES and 4007ES Hybrid Fire Alarm Systems Programmer s Manual 579 1167 Rev D...
Page 2: ......
Page 4: ......
Page 10: ......
Page 18: ......
Page 36: ......
Page 56: ......
Page 122: ...9 38...
Page 132: ......
Page 134: ......
Page 150: ......
Page 166: ...A 16...
Page 167: ......