3. Technical data
Table 1: Electrical characteristics
Actuator type
Folding Arm² 530
Folding Arm² 710
Folding
Arm² 960
Folding
Arm² 1200
KL²-K-50 KL²-K-80
KL²-50
KL²-80
KL²-100
KL²-M
KL²-L
Rated voltage
24 V DC
Permissible rated voltage range
24 V DC ±15 %
Ripple of rated voltage Vpp
max. 500 mV
Undervoltage detection
yes
Rated current
(1)
1.4 A
2.0 A
2.0 A
2.6 A
3.0 A
3.0 A
3.0 A
Maximum starting current “OPEN”
1.54 A
2.2 A
2.2 A
2.9 A
3.3 A
3.3 A
3.3 A
Maximum starting current “CLOSE”
1.54 A
2.2 A
2.2 A
2.0 A
2.0 A
2.0 A
2.0 A
Maximum cut-off current in “OPENING”
direction
(2)
1.4 A
2.0 A
2.0 A
2.6 A
3.0 A
3.0 A
3.0 A
Maximum cut-off current in “CLOSING”
direction
(2)
1.4 A
2.0 A
2.0 A
1.7 A
1.7 A
1.7 A
1.7 A
Current consumption after cut-off
(closed current)
65 mA
Cut-off via
built-in electronic overload cut-off
Maximum permissible number of actuator units
connected in parallel
(3)
4
Cable length between two actuators
in synchro mode
max. 10 m
Stopping time
(4)
3 s
Protection class
III
(1)
Maximum current consumption with nominal load.
(2)
Delivery condition, can be parameterized with SICO LINK.
(3)
Maximum cable length for bus communication between two actuators.
(4)
Within a SICO synchro group the stopping time indicates how long operable actuators are running when one connected actuator fails or cuts off.
Table 2: Volt-free contact (NO1 / NO2)
Actuator type
Folding Arm²
Rated voltage
max. 28 V DC
Relay contact load
2 A
The normally open contact (NO) is only switched when the
actuator is cut off in the “CLOSE” end position. This means
that the signal is stroke-dependent and can be evaluated as
a “CLOSE signal”.
ATTENTION
The maximum contact load must not be exceeded.
Table 3: Connection and operation
Actuator type
Folding Arm² 530
Folding Arm² 710
Folding
Arm² 960
Folding
Arm² 1200
KL²-K-50 KL²-K-80
KL²-50
KL²-80
KL²-100
KL²-M
KL²-L
Pause time during change of direction
(1)
500 ms
Switch-on duration
S2 ED 30 % (short-time duty 3 of 10 minutes)
Stability of opening and closing cycles
> 11 000
Sound level
(2)
< 70 dB (A)
Multiple triggering according to
prEN 12101-9 / ISO 21927-9
allowed
Multiple triggering after stop
allowed
Maintenance
See the attached sheet “safety instructions and warranty conditions”!
(1)
For the direction change (pole-change), it is necessary that the power supply ensures a pause time (zero volt range) of at least 500 ms
.
(2)
Measured at a distance of one metre under normal conditions.