ADDR
FUNC
REG H,L
COUNT H,L
CRC L,H
01
03
00
21
00
01
D4
00
The answer:
ADDR
FUNC
BYTE C
DATA H,L
CRC L,H
01
03
02
DATA - identification code (23DEh)
3. Change of the device address from 1 to 2 (write to reg. 20h)
ADDR
FUNC
REG H,L
DATA H,L
CRC L,H
01
06
00
20
00
02
09
C1
DATA H - 0
DATA L - new device address (2)
The answer (the same as the message):
ADDR
FUNC
REG H,L
DATA H,L
CRC L,H
01
06
00
20
00
02
09
C1
4. Change of baud rate of all devices connected to the net (BROADCAST message).
ADDR
FUNC
REG H,L
COUNT H,L
CRC L,H
00
06
00
22
00
04
29
D2
DATA H - 0
DATA L - 4, new baud rate 19200 baud
Device do not reply to BROADCAST-type messages.
5. Read of the registers 1, 2 and 3 in one message (example of reading a number of
registries in one frame):
ADDR
FUNC
REG H,L
COUNT H,L
CRC L,H
01
03
00
01
00
03
54
0B
COUNT L - the count of being read registers (max.16)
The answer:
57
i