User manual - RATEMETER STI-94
Register Write
Range
Register description
58h
Yes
0 ÷ 2
“ALArmS”
parameter in
“rELAy3”
menu:
0
- no changes;
1
- on;
2
- off
59h
5Ah
Yes
Yes
0 ÷ 999999
“
SEt P2
” parameter in “
rELAy3
” menu, no decimal point included
Parameters or relay R4 operation
60h
61h
Yes
Yes
0 ÷ 999999
“
SEt P
” parameter in “
rELAy4
” menu, no decimal point included
62h
63h
Yes
Yes
0 ÷ 99999
“
HySt
” parameter in “
rELAy4
” menu, no decimal point included
64h
Yes
0 ÷ 5
“
modE
” parameter in “
rELAy4
” menu:
0
- “
noACt
” mode;
1
- “
on
” mode;
2
- “
oFF
” mode;
3
- “
in
” mode;
4
- “
out
” mode;
5
- “
modbuS
” mode
65h
Yes
0 ÷ 999
“t on”
parameter in
“rELAy4”
menu, expressed in tenth of seconds
or tenth of minutes depend on
“unit”
parameter
66h
Yes
0 ÷ 999
“t oFF”
parameter in
“rELAy4”
menu, expressed in tenth of
seconds or tenth of minutes depend on
“unit”
parameter
67h
Yes
0 ÷ 1
“unit”
parameter in
“rELAy4”
menu:
0
- seconds;
1
- minutes
68h
Yes
0 ÷ 2
“ALArmS”
parameter in
“rELAy4”
menu:
0
- no changes;
1
- on;
2
- off
69h
6Ah
Yes
Yes
0 ÷ 999999
“
SEt P2
” parameter in “
rELAy4
” menu, no decimal point included
70h
Yes
0 ÷ 1
“
modE
” parameter in “
HOLd
” menu (type of detected changes):
0
- peaks;
1
- drops
71h
72h
Yes
0 ÷ 999999
“
PEA
” parameter in “
HOLd
” menu (minimum detectable change, no
decimal point included)
73h
Yes
0 ÷ 199
“
timE
” parameter in “
HOLd
” menu,
maximum peaks' (or drops')
display time expressed in seconds
74h
Yes
0 ÷ 1
“
HdiS
” parameter in “
HOLd
” menu (the type of values displayed on
the display
):
0
- current measurement value;
1
- peaks (or drops) values
75h
Yes
0 ÷ 1
“
H r1
” parameter in “
HOLd
” menu (the control mode of relay R1 and
LED R1)
:
0
- control depends on current measurement values;
1
- control depends on peaks (or drops) values;
76h
Yes
0 ÷ 1
“
H r2
” parameter in “
HOLd
” menu (the control mode of relay R2 and
LED R2) :
0
- control depends on current measurement values;
1
- control depends on peaks (or drops) values;
77h
Yes
0 ÷ 1
“
H r3
” parameter in “
HOLd
” menu (the control mode of relay R3 and
LED R3) :
0
- control depends on current measurement values;
1
- control depends on peaks (or drops) values;
43