User manual - METER SRT-457
rESP
- this parameter defines minimal (additional) delay between the Modbus message
and the answer of the device (received and sent via RS-485 interface). This
additional delay allows the device to work with poor RS-converters which do not
works properly on baud rates higher than 19200. This parameter can be set to one
of values:
Std
- answer as quick as possible, no additional delay
10c
20c
50c
100c
200c
- answer delayed of 10, 20, 50, 100 of 200 chars respectively, where
one character time depends on selected baud rate
In the most cases parameter
rESP
should be set to
Std
(no additional delay).
Unfortunately for some third party RS-converters
rESP
should be adjusted
experimentally. Table 7.1 contains most frequently used values.
bAud parameter
38.4
57.6
115.2
rESP parameter
10c
20c
50c
Tab.7.1.
Settings of
rESP
parameter
7.3.8.
Edit
paramet
er
This parameter allows to change the edition mode of numerical parameters:
dig
- the change to by digit mode,
Slid
- slide change mode.
7.3.9.
dEFS
parameter
This setting allows to restore the factory settings of the device. To get the access to this
option special password is required: 5465 , next the device displays acknowledge question
SEt?
. Press
[ENTER]
to acknowledge the restoring of factory settings or
[ESC]
to cancel.
7.3.10.
SErv menu
This menu contains the parameters for authorized service only. To enter this menu
proper service password must be entered. Improper settings can causes of damage of the
device.
25