User manual - METER SRP-147
Figure 10.7 The volume characteristic of tank depending on input current in 4÷20mA range.
Example 9
: Current output value calculation
Let the current output parameters be:
“modE”
=
“4-20”
,
“OUtL”
= 100,
“OUtH”
= 200,
“Lo r”
= 5.0,
“Hi r”
= 5.0
Parameters
“Lo r”
and
“Hi r”
define working range of current output to 3.8 ÷ 21 mA.
Output current will be calculated for three displayed values „D”:
a) D = „17.5”
According to formula from page 35:
I
out
= (17.5-10.0) / (20.0-10.0) × 16 mA + 4 mA = 0.75 ·16 + 4 = 16 mA
Calculated I
out
do not exceeds the output working range (3.8 - 21 mA).
b) D = „20.5”
According to formula from page 35:
I
out
= (20.5-10.0) / (20.0-10.0) × 16 mA + 4 mA = 1.05 ·16 + 4 = 20.08 mA
Calculated I
out
do not exceeds the output working range (3.8 - 21 mA).
c) D = „30.0”
According to formula from page 35:
I
out
= (30.0-10.0) / (20.0-10.0) × 16 mA + 4 mA = 2 ·16 + 4 = 36 mA.
Calculated I
out
exceeds the output working range (3 - 21 mA), so current output will generate
current equal to the upper border of range defined by parameter
“Lo r”
i
“Hi r”
(it means
21 mA).
50
3
4
5
6
7
8
9
10
0
10
20
30
40
50
60
70
80
I [mA]
V
[m