background image

Assisting the automation

industry since 1986   

User manual

COUNTER  

SLB-94

Firmware: v.8.03 or higher
Input type: pulse
Internal cycles and totalizer function counter

 2013.02.20

SLB-94_INSSXEN_v.2.04.000 

Microlectra bv.

Read the user's manual carefully before starting to use the unit or software. 

Producer reserves the right to implement changes without prior notice.

Microlectra bv.

Hermanus Boerhaavestraat 6.   3261 ME Oud-Beijerland.  Netherlands.

Tel 31(0)186-616290     Fax 31(0)186-610349          www.microlectra.nl     [email protected]

Summary of Contents for SLB-94

Page 1: ...ter 2013 02 20 SLB 94_INSSXEN_v 2 04 000 Microlectra bv Read the user s manual carefully before starting to use the unit or software Producer reserves the right to implement changes without prior noti...

Page 2: ...3 7 2 PARAMETERS EDITION 24 7 2 1 Numeric parameters digit change mode 24 7 2 2 Numeric parameters slide change mode 24 7 2 3 Switch parameters LIST type 24 7 3 MENU DESCRIPTION 25 7 3 1 rELAy1 rELAy4...

Page 3: ...ulations GND input of device should be connected to PE wire The unit must be properly set up according to the application Incorrect configuration can cause defective operation which can lead to unit d...

Page 4: ...coefficients mul div offset point it means profiles these profiles make recalculation between units easier Main counter range is limited from 99999 to 999999 Build in totalizer is 12 digits long 9999...

Page 5: ...ounter 99 999 999 999 plus decimal point 0 999 999 plus decimal point 99 999 999 999 999 999 999 999 Communication interface RS 485 8N1 and 8N2 Modbus RTU not separated Baud rate 1200 bit s 115200 bit...

Page 6: ...l advantage of these characteristics installation of the unit must be conducted correctly and according to the local regulations Read the basic safety requirements on page 3 prior to starting the inst...

Page 7: ...mm mounting hole Figure 4 1 4 2 must be prepared The thickness of the material of which the panel is made must not exceed 5mm When preparing the mounting hole take the grooves for catches located on...

Page 8: ...2 Allowable mounting hole dimensions Figure 4 3 Installing of brackets and dimensions of connectors Figure 4 4 Minimum distances when assembly of a number of units 8 115 mm 67 mm 92 mm 5 mm 12 mm 10 m...

Page 9: ...ust be terminated with appropriate insulated cable tips Tighten the clamping screws The recommended tightening torque is 0 5 Nm Loose screws can cause fire or defective operation Over tightening can l...

Page 10: ...ing then additional safety circuits are required In the case of interference from the power supply side the use of appropriate anti interference filters is recommended Bear in mind that the connection...

Page 11: ...nding on device version particular terminal can be marked according to the top or bottom number Figure 4 5 Terminals description relay outputs Description of control signals symbols A counting input B...

Page 12: ...0V AC DC or 19 24 50V DC 16 24 35V AC Figure 4 8 Connection of power supply and relays 12 R4 FUSE 1 2 L N L N 10 11 12 13 14 15 3 4 FUSE R1 R2 R3 1 2 5 6 7 8 9 GND DATA DATA RS 485 Uo 24V 5 10 Imax 10...

Page 13: ...eries with 100R 5W resistor connected in parallel to relay terminals or better directly on the load In consequence of using the suppression circuit the level of generated electromagnetic disturbances...

Page 14: ...xcessively high temperatures cause faster ageing of the internal components and shorten the fault free time of unit operation In cases where the unit gets dirty do not clean with solvents For cleaning...

Page 15: ...parameter being edited Symbol used in the manual Functions Change of the present menu Modification of the parameter value Change of display mode Symbol used in the manual v Functions Change of the pr...

Page 16: ...modE parameter in CyCLE menu In case when contents of any counter exceeds permissible range the counter continues counting after roll off and overload is signalised If the result is out of permissibl...

Page 17: ...in menu mode but relays controlling and autoreset function are frozen for about 0 1 sec while storing the parameters in menu mode 6 2 SELECTING OF DISPLAYED VALUE The SLB 94 counter allows counting i...

Page 18: ...position is limited to four digits 0 0000 The SLB 94 counter can store which half of the totalizer is selected to be displayed If more significant half is selected and user goes to other counters val...

Page 19: ...ding of time periods of the pulses The filter can be set to blocking frequencies higher than 10 20 30 40 50 60 70 80 and 90Hz The time periods of stable states 0 t0 and 1 t1 of pulses must be not shor...

Page 20: ...ab 6 1 Time periods t0 t1 depend on filtered frequency When the filter is turned off time periods t0 i t1 must be longer than 50 s see Figure 6 4 and maximum counted frequency is equal 10 kHz a b Figu...

Page 21: ...lue reaches or exceeds the threshold for up counting points A C E G The active state of the relay close or open is defined by parameter modE Relays R3 and R4 can be controlled due to result of main co...

Page 22: ...s up and reaches threshold If parameter timE 0 and AUTORESET function is active particular relay will not change it s state to active If alarm situation occurs e g counter value is greater than allowa...

Page 23: ...check confirmed changes or switch viewed parameter pressing v button 7 1 PROGRAMMING MENU To enter main menu being in the measurement mode operator must to press and hold at least 2 sec ESC MENU butt...

Page 24: ...easing button v can be used If v is pressed shortly and button is still pressed increasing slow down for a moment only if v is pressed and held while button is still pressed the increasing slow down a...

Page 25: ...tering of password If entered password is correct first menu position else warning Error will be displayed and unit returns to measurement mode Due to problem with direct displaying of m letter it is...

Page 26: ...0 0 the relay stays active as long as the result is same or higher of the particular threshold value While parameter timE 1 0 and AUTORESET is active relay R1 will not change its state to active or du...

Page 27: ...ilable in ALL EL and mAn modes too ArES m this parameter enables the auto zeroing mode AUTORESET function AUTORESET clears main counter when it reaches the value equal to SEtP 1 This parameter can be...

Page 28: ...alizer can be done via RS 485 interface by presets of some registers with value 0000h Remote zeroing is available in ALL EL and mAn modes too 7 3 5 PrESCA menu This menu contains parameter which confi...

Page 29: ...parameter sets the access to the configuration registers of the device Possible values on configuration registers can be set via RS 485 interface oFF configuration registers can not be set via RS 485...

Page 30: ...he access to the menu is possible by the one use password To get this password please contact with Marketing Division Single use password can be used only one time after that it is destroyed Entering...

Page 31: ...Counting mode rELPr1 Value of threshold 4 edition of threshold value if allowed ProFiL Profile number profile change if allowed mEmo1 Zeroing memory 1 mEmo5 Zeroing memory 5 rELPr2 rELPr4 mEmo2 mEmo3...

Page 32: ...digit mode Slid slide change mode 7 3 10 dEFS parameter This setting allows to restore the factory settings of the device To get the access to this option special password is required 5465 next the d...

Page 33: ...to rELAy1 menu rELAy4 MENU ESC ENTER MENU ESC Options similar to rELAy3 menu rELAy3 MENU ESC timE 3 ENTER MENU ESC ENTER ENTER MENU ESC SEtPr1 modE 1 unit 1 Parameter edition timE 1 SEtPr3 See next pa...

Page 34: ...eter edition ENTER MENU ESC ENTER ENTER MENU ESC Addr bAud A rEL2 A rEL3 A rEL4 Parameter edition ENTER MENU ESC ENTER ENTER MENU ESC SEtCod A rEL1 See previous page MENU ESC SEt 4 digit special passw...

Page 35: ...owed in Figure 8 1 is proposed to realize this task Settings Main counter settings relay R1 threshold 16 16 pcs for layer time 1 0 sec mode on autoreset on reset ALL Cycles counter relay R2 threshold...

Page 36: ...rcuit diagram 36 COM A RESET permission for assembly line start 5 6 7 8 9 START 24V DC supply B C Contact sensor A Distance piece placement Line stop Assembly line start permission Assembly line start...

Page 37: ...1 No 02h1 No 03h1 No depend on value type Display value first higher word Display value second word Display value third lower word 04h Yes see descr High byte type of the displayed value reg 01h 02h 0...

Page 38: ...S menu cycles counter reset source 0 ALL 1 EL reset with REST input and RS 485 interface 2 mAn reset with RESET button and RS 485 interface 3 nonE reset with RS 485 interface only 14h Yes 0 3 rES t pa...

Page 39: ...4 A ProF parameter 25h Yes 0 5 rESP parameter in rS 485 menu additional response delay 0 no additional delay 1 10c option 2 20c option 3 50c option 4 100c option 5 200c option 27h Yes 0 99 mbtimE par...

Page 40: ...e descr The totalizer most significant word 55h No see descr The totalizer medium significant word 56h No see descr The totalizer least significant word 60h Yes 0 1 modE parameter in CyCLE menu cycles...

Page 41: ...of 0000h to these registers 04h 0Dh causes by zeroing of main counter and precounter content 3 after writing to register no 20h the device responds with an old address in the message 4 after writing t...

Page 42: ...e BYTE C Data byte count in answer frame DATA H L Data byte Hi and Lo byte CRC L H CRC error check Hi and Lo byte 1 Read of device ID code ADDR FUNC REG H L COUNT H L CRC L H 01 03 00 21 00 01 D4 00 T...

Page 43: ...R FUNC REG H L COUNT H L CRC L H 01 03 00 01 00 01 D5 CA Response while normal operation no errors ADDR FUNC BYTE C DATA H L CRC L H 01 03 02 00 00 B8 4C DATA H L 0000h 0 higher word of displayed valu...

Page 44: ...DDR FUNC REG H L DATA H L CRC L H 01 06 00 22 00 09 E9 C6 DATA L 9 value exceeds allowable range 0 7 The answer exception code 03h illegal data value ADDR FUNC ERR CRC L H 01 86 03 02 61 There is no f...

Page 45: ...P 3 Relay threshold 2000 25 modE 3 Operation mode of relay on 26 timE 3 The time period of the relay active state 1 0 26 unit 3 Unit of timE parameter SEC 26 Parameters of relay R4 operation rELAy4 me...

Page 46: ...9 rESP Additional delay of answer transmission Std 29 Settings of access to the configuration parameters SECu menu A rEL1 Permission to changes of relay R1 threshold without of the user password knowl...

Page 47: ...User manual COUNTER SLB 94 47...

Page 48: ...lectra bv Hermanus Boerhaavestraat 6 3261 ME Oud Beijerland Netherlands Tel 31 0 186 616290 Fax 31 0 186 610349 www microlectra nl info microlectra nl www microlectra nl Microlectra bv info microlectr...

Reviews: