User manual - MODULE SIN-8
1. Read of device ID code
ADDR
FUNC
REG H,L
COUNT H,L
CRC L,H
01
03
00
21
00
01
D4
00
The answer:
ADDR
FUNC
BYTE C
DATA H,L
CRC L,H
01
03
02
00
8B
F8
23
DATA - identification code (008Bh)
2. Change of the device address from 1 to 2 (write to reg. 20h)
ADDR
FUNC
REG H,L
DATA H,L
CRC L,H
01
06
00
20
00
02
09
C1
DATA H - 0
DATA L - new device address (2)
The answer (the same as the message):
ADDR
FUNC
REG H,L
DATA H,L
CRC L,H
01
06
00
20
00
02
09
C1
3. Reading of input 5 current state.
ADDR
FUNC
REG H,L
COUNT H,L
CRC L,H
01
03
00
05
00
01
94
0B
Answer:
ADDR
FUNC
BYTE C
DATA H,L
CRC L,H
01
03
02
00
01
79
84
DATA H, L - input state (1 – it means that high state is delivered to input 5)
There is no full implementation of the Modbus Protocol in the device. The functions
presented above are available only.
10