Simex Simpact SLIK-73 User Manual Download Page 8

User manual for universal counter with batching function SLIK-73

4.3. 

  

CONNECTION METHOD

  

Caution

- Installation should be conducted by qualified personnel . During installation all 

available safety requirements should be considered. The fitter is responsible for 

executing the installation according to this manual, local safety and EMC 

regulations.

- The unit is not equipped with an internal fuse or power supply circuit breaker. 

Because of this an external time-delay cut-out fuse with minimal possible nominal 

current value must be used (recommended bipolar, max. 2A) and a power supply 

circuit-breaker located near the unit. In the case of using a monopolar fuse it must 

be mounted on the phase cable (L).

- The power supply network cable diameter must be selected in such a way that in 

the case of a short circuit of the cable from the side of the unit the cable shall be 

protected against destruction with an electrical installation fuse. 

- Wiring must meet appropriate standards and local regulations and laws.

 

- In order to secure against accidental short circuit the connection cables must be 

terminated with appropriate insulated cable tips. 

- Tighten the clamping screws. The recommended tightening torque is 0.5 Nm. 

Loose screws can cause fire or defective operation. Over tightening can lead to 

damaging the connections inside the units and breaking the thread.

- In the case of the unit being fitted with separable clamps they should be inserted 

into appropriate connectors in the unit, even if they are not used for any 

connections. 

- Unused clamps (marked as n.c.) must not be used for connecting any 
connecting cables (e.g. as bridges), because this can cause damage to the 
equipment or electric shock. 

- If the unit is equipped with housing, covers and sealing packing, protecting 

against water intrusion, pay special attention to their correct tightening or clamping. 

In the case of any doubt consider using additional preventive measures (covers, 

roofing, seals, etc.). Carelessly executed assembly can increase the risk of electric 

shock.     

- After the installation is completed do not touch the unit’s connections when it is 

switched on, because it carries the risk of electrical shock. 

Due to possible significant interference in industrial installations appropriate measures 
assuring correct operation of the unit must be applied.  To avoid the unit of improper 
indications keep recommendations listed below.

Avoid common (parallel) leading of signal cables and transmission cables together with 

power supply cables and cables controlling induction loads (e.g. contactors). Such cables 

should cross at a right angle.

Contactor coils and induction loads should be equipped with anti-interference protection 

systems, e.g. RC-type.

8

!

Summary of Contents for Simpact SLIK-73

Page 1: ...unter with batching function family type SLIK 73 firmware version 7 03 or higher Read the user s manual carefully before starting to use the unit Producer reserves the right to implement changes witho...

Page 2: ...N 22 7 2 1 Numeric parameters digit change mode 22 7 2 2 Numeric parameters slide change mode 22 7 2 3 Switch parameters LIST type 23 7 3 MENU DESCRIPTION 23 7 3 1 rELAy menu 24 7 3 2 Pr inP parameter...

Page 3: ...ng to the application Incorrect configuration can cause defective operation which can lead to unit damage or an accident If in the case of a defect of unit operation there is a risk of a serious threa...

Page 4: ...s by host and allows use of unit in advanced network systems Two counting inputs pulse inputs can operate in few different modes as two independent pulse inputs or single quadrature input Additional p...

Page 5: ...ousing material Housing dimensions Mounting hole Assembly depth Panel thickness panel NORYL GFN2S E1 72 x 36 x 97 mm 66 5 x 32 5 mm min 102 mm max 5 mm Operating temperature Storage temperature Humidi...

Page 6: ...st be immediately reported to the carrier Also write down the unit serial number on the housing and report the damage to the manufacturer Attached with the unit please find user s manual warranty asse...

Page 7: ...igure 4 1 Mounting hole dimensions Figure 4 2 Installing of brackets and dimensions of connectors Figure 4 3 Minimum distances when assembly of a number of units 7 5 mm 92 mm 12 mm 10 mm 16 mm 8 5 mm...

Page 8: ...operation Over tightening can lead to damaging the connections inside the units and breaking the thread In the case of the unit being fitted with separable clamps they should be inserted into appropri...

Page 9: ...e unit should be as short as possible and the metal housing of the filter must be connected to the earthing with largest possible surface The cables connected to the filter output must not run in para...

Page 10: ...ductive loads coils contactors power relays electromagnets motors etc it is required to use additional suppression circuit typically capacitor 47nF min 250VAC in series with 100R 5W resistor connected...

Page 11: ...type outputs connection Construction of counter s inputs allows connecting of pulser with common earth Figure 4 10 a or common plus Figure 4 10 b without additional intermediary circuits sensor with N...

Page 12: ...he internal components and shorten the fault free time of unit operation In cases where the unit gets dirty do not clean with solvents For cleaning use warm water with small amount of detergent or in...

Page 13: ...parameter Enter to the sub menu Confirmation of changes made in parameter being edited Symbol used in the manual Functions Change of the present menu Modification of the parameter value Monitoring of...

Page 14: ...epends on selected function There are available four functions addition of pulses from A and B inputs Funct A b subtraction of pulses from A and B inputs Funct A b quadrature counting with standard re...

Page 15: ...k to the measurement mode If a thresholds values free access is enabled or thresholds and offset values free access is enabled see SECu menu user can change the value of particular parameter pressing...

Page 16: ...no active A and B quAd 1 or quAd 4 other than dirEct any B and A quAd 1 or quAd 4 dirEct active Tab 6 1 Possible configurations while use device as a batcher Amount of poured fluid can be changed by p...

Page 17: ...counting is providing of time periods of the pulses The filter can be set to blocking frequencies higher than 10 20 30 40 50 60 70 80 and 90Hz The time periods of stable states 0 t0 and 1 t1 of pulses...

Page 18: ...60 Hz 70 7 2 ms 70 Hz 80 6 3 ms 80 Hz 90 5 6 ms 90 Hz Tab 6 2 Time periods t0 t1 depend on filtered frequency When the filter is turned off time periods t0 i t1 must be longer than 50 s see Figure 6...

Page 19: ...timE parameter tZ delay of relay reaction Figure 6 5 Principle of relay outputs operation Parameter SEtP defines threshold of relay trace a While normal operation of counter relay output can change it...

Page 20: ...t to 0 than relay stays in active state periods tA tC tE tG as long as counter value is equal or higher than threshold value traces b c If parameter timE is set to value different from 0 than relay st...

Page 21: ...surement mode If a thresholds values free access is enabled or thresholds and offset values free access is enabled see SECu menu user can change the value of particular parameter pressing button ENTER...

Page 22: ...ys or v causes change of current position flashing digit or the sign Short pressing of the ENTER button causes change of the position digit Press ENTER at least 2 seconds to accept the changes after t...

Page 23: ...meter change of current flashing digit slide change of value acceleration deceleration direction change While editing switch parameter selection of switch parameter If numerical parameter is being edi...

Page 24: ...nd timE When a particular LED lights its mean the relay is closed If parameter modE is set to modbuS value after power supply off and on again relays are open timE the time period of the relay active...

Page 25: ...he RESET button on the front panel This operation must to be approved by ENTER button After zeroing counter displays value equals to oFFSEt parameter In this mode electronic reset is disabled nonE thi...

Page 26: ...of inputs A and B as quadrature input with normal resolution it means that counter is incremented decremented by 1 every single quadrature cycle on inputs A and B qUAd 4 quadrature mode 4 This option...

Page 27: ...99 If the value 0 is set then device responds to frames with address 255 FFh bAud this parameter determines RS 485 interface baud rate It can be set to one of 8 possible values 1 2 2 4 4 8 9 6 19 2 38...

Page 28: ...availability of other parameters SEtCod user password 4 digits number If this parameter is set at value 0000 user password is turned off If the user do not remember his password the access to the men...

Page 29: ...FFS value it is possible to use two different operation modes of quick view see Figure 7 1 Figure 7 2 Number of accessible parameters for viewing edition depends on device version Figure 7 1 Operation...

Page 30: ...ter allows to change the edition mode of numerical parameters dig the change to by digit mode Slid slide change mode 7 3 12 dEFS parameter This setting allows to restore the factory settings of the de...

Page 31: ...at least 2 seconds MENU ESC ENTER MENU ESC MENU ESC rELAy Measurement mode MENU ESC Pr inP MENU ESC rESEt ENTER MENU ESC ENTER ENTER MENU ESC SEtP modE unit Parameter edition See next page ENTER MENU...

Page 32: ...ESC dEFS ENTER MENU ESC Parameter edition ENTER MENU ESC ENTER ENTER MENU ESC Addr bAud mbAccE mbtimE rESP See previous page MENU ESC SEt 4 digit special password entering 0 _ _ _ ENTER ENTER Default...

Page 33: ...1 revolution 100 pulses Settings mul 50 div 100 oFFset 0 point 0 0 Example 3 counter SLIK 73 used in batcher function see Figure 6 2 6 3 Data flow meter 100 pulses L main valve flow valve 1 about 10...

Page 34: ...0 to 115200 bits second Transmission protocol MODBUS RTU compatible The device parameters and display value are available via RS 485 interface as HOLDING type registers numeric values are given in U2...

Page 35: ...ace only 13h Yes 0 1 ArESEt option main counter autoreset 0 oFF autoreset disabled 1 on enabled 14h Yes 0 9 FiLtEr option filtering rate 0 for input signal up to 10kHz frequency 1 up to 10Hz 2 up to 2...

Page 36: ...ess 2Fh Yes 0 1 Edit parameter numerical parameters edit mode 0 dig mode 1 SLid mode 30h6 Yes see descr SEtP parameter in rELAy menu high word 31h6 Yes see descr SEtP parameter in rELAy menu low word...

Page 37: ...rection 9 2 TRANSMISSION ERRORS DESCRIPTION If an error occurs while write or read of single register then the device sends an error code according to Modbus RTU specifications Error codes 01h illegal...

Page 38: ...connected to the net BROADCAST message ADDR FUNC REG H L COUNT H L CRC L H 00 06 00 22 00 04 29 D2 DATA H 0 DATA L 4 new baud rate 19200 baud Device do not reply to BROADCAST type messages 4 Read of t...

Page 39: ...TA H L CRC L H 01 06 00 11 00 01 18 0F The answer the same as the message ADDR FUNC REG H L DATA H L CRC L H 01 06 00 11 00 01 18 0F 7 Try to write illegal data value into baud rate register ADDR FUNC...

Page 40: ...ngs menu PrESCA muL multiplier 1 26 div divider 1 26 oFFSEt Offset constant value added to the result to move the zero point of the current scale 0 26 Point Decimal point position 0 00 26 RS 485 inter...

Page 41: ...User manual for universal counter with batching function SLIK 73 41...

Page 42: ...User manual for universal counter with batching function SLIK 73 42...

Page 43: ...User manual for universal counter with batching function SLIK 73 43...

Page 44: ...SIMEX SIMEX Sp z o o ul Wielopole 7 PL 80 556 Gda sk Poland tel 48 58 762 07 77 fax 48 58 762 07 70 http www simex com pl e mail info simex com pl...

Reviews: