User manual - CONTROLLER PUR-94D
Register
Write
Range
Register description
5Bh
Yes
0 ÷ 999
“toFF”
parameter in
“rEL3”
menu, expressed in tenth of seconds
or tenth of minutes depend on
“unit”
parameter - register no. 58h)
5Ch
Yes
0 ÷ 1
“unit”
parameter in
“rEL3”
menu:
0
- seconds;
1
- minutes
5Dh
Yes
0 ÷ 2
“AL”
parameter in
“rEL3”
menu (only when
rEL3
is relay output):
0
- no changes;
1
- on;
2
- off
5Eh
Yes
-999 ÷ 9999 “
SEt2
” parameter in “
rEL3
” menu, no decimal point included
5Fh
Yes
-999 ÷ 9999 “
InLo
” parameter in “
rEL3
” menu, no decimal point included
60h
Yes
-999 ÷ 9999 “
InHi
” parameter in “
rEL3
” menu, no decimal point included
61h
Yes
0 ÷ 9999
“
PEri
” parameter in “
rEL3
” menu, no decimal point included
62h
Yes
0 ÷ 9999
“
H on
” parameter in “
rEL3
” menu, no decimal point included
63h
Yes
0 ÷ 9999
“
HoFF
” parameter in “
rEL3
” menu, no decimal point included
64h
Yes
0 ÷ 1
“
Acti
” parameter in “
AL
” menu, (only when
rEL3
is OC-type output):
0
-
“
noCH
” option
;
1
-
“
USdu
” option
;
65h
Yes
0 ÷ 1000
“
duty
” parameter in “
AL
” menu (only when
rEL3
is OC-type output)
66h
Yes
0 ÷ 1000
Current OC type output fill factor expressed as a percentage without
the decimal point (only where
rEL3
is the OC type output)
67h
Yes
-999 ÷ 9999 “
OFFS
” parameter in “
rEL3
” menu, no decimal point included
68h
Yes
0 ÷ 1000
“
SEnS
” parameter in“
rEL3
” menu, no decimal point included
69h
Yes
0 ÷ 3
“
Sour
” parameter in “
rEL4
” menu:
0
- “
InPU
” option;
1
- “
modb
” option;
2
- “
PidH
” option;
3
- “
PidC
”
option;
6Ah
Yes
0 ÷ 5
“
modE
” parameter in “
rEL4
” menu:
0
- “
noAC
” mode;
1
- “
on
” mode;
2
- “
oFF
” mode;
3
- “
in
” mode;
4
- “
out
” mode;
5
- “
PULS
” mode
6Bh
Yes
-999 ÷ 9999 “
SEtP
” parameter in “
rEL4
” menu, no decimal point included
6Ch
Yes
-999 ÷ 999
“
HySt
” parameter in “
rEL4
” menu, no decimal point included
6Dh
Yes
0 ÷ 999
“t on”
parameter in
“rEL4”
menu, expressed in tenth of seconds or
tenth of minutes depend on
“unit”
parameter - register no. 69h)
6Eh
Yes
0 ÷ 999
“toFF”
parameter in
“rEL4”
menu, expressed in tenth of seconds
or tenth of minutes depend on
“unit”
parameter - register no. 69h)
6Fh
Yes
0 ÷ 1
“unit”
parameter in
“rEL4”
menu:
0
- seconds;
1
- minutes
70h
Yes
0 ÷ 2
“AL”
parameter in
“rEL4”
menu (only when
rEL4
is relay output):
0
- no changes;
1
- on;
2
- off
71h
Yes
-999 ÷ 9999 “
SEt2
” parameter in “
rEL4
” menu, no decimal point included
72h
Yes
-999 ÷ 9999 “
InLo
” parameter in “
rEL4
” menu, no decimal point included
73h
Yes
-999 ÷ 9999 “
InHi
” parameter in “
rEL4
” menu, no decimal point included
74h
Yes
0 ÷ 9999
“
PEri
” parameter in “
rEL4
” menu, no decimal point included
67